| Part number | AGC-12-R |
| Body | Glass tube, 1/4 x 1-1/4 in (6.3 x 32 mm) |
| Rated current | 12 A |
| End caps | nickel-plated brass |
| Typical voltage drop | 0.138 V |
| AC interrupting rating | 1,000 A at 32 Vac |
| Element | single element |
| Design standard | UL 248-14 |
| Typical melting I2t | 696.96 A²s |
| Typical DC cold resistance | 0.006 Ω |
| Voltage rating | 32 Vac |
| Breaking capacity | 35 A at 250 Vac up to 3 A, 100 A at 250 Vac from 1-1/4 A, 1,000 A at 32 Vac |
A fast-acting fuse is a single element sized to melt quickly once the current passes its rating. There is no thermal mass held back for a surge, so the response to an overload is immediate and the response to an inrush is equally immediate - the two are the same event as far as the element is concerned.
The secondary columns are where the engineering hides. The typical cold resistance is 0.006 Ω, which is what the circuit sees before the element warms. Melting takes 696.96 A²s, so a fault has to deliver that much energy before the element even starts to go. At rated current the drop across it is 0.138 V. The current and voltage ratings only say when they matter.
AGC is the family and 12 is the ampere rating, 12 A. The trailing -R marks the RoHS version; a packaging prefix such as BK- or BK1- may be added in front, which alters the quantity per box only.
Above roughly ten amps the fuse is protecting wiring and busbars rather than a component. The relevant question stops being "will it open" and becomes "what does it let through while it opens", which is what the I2t figure describes.
The step below is AGC-10-R at 10 A, the step above is AGC-14-R at 14 A. Between the three the body, the end caps and the breaking capacity are identical; only the element changes, so the choice is the load current and nothing else.
UL Listed and CSA certified (Guide JDYX, File E19180).
Where the equipment ships into several markets, check each approval separately - the European and North American marks on this family do not always cover the same current range, and the gap is usually at the top of the range.
AGC is the fast-acting half of the MDL/AGC pair. Putting an AGC into a motor circuit that was engineered around MDL will nuisance-trip on every start, and the usual response - fitting a bigger AGC - removes the protection the circuit was designed for.
For a like-for-like replacement, match three things: 12 A, fast-acting speed, and a voltage rating at least as high as the circuit can apply. Everything else about the part - the cap plating, the marking, the packaging prefix - is a purchasing detail rather than an electrical one.
What is the difference between 3AG and 3AB?
Both are 1/4 x 1-1/4 in. 3AG is the glass body, 3AB is the ceramic one. The footprint is identical; the breaking capacity is not.
What happens if I fit a lower rating?
It will open on normal load, usually at the least convenient moment. A fuse is not a safety margin to be tightened - it is sized to the cable and the load, and reducing it does not add protection, it adds failures.
Why does the table list several breaking capacities?
Because the fuse is asked to interrupt different currents at different voltages. The 250 Vac figure is usually the smallest and the 32 V figure the largest, since a low voltage is much easier to break than a high one.
Design note: the ratings above are Technical Data 2543. Verify the exact rating, the voltage at which the breaking capacity applies, and the certificate for this current before release.