140FEE Eaton Bussmann 690VAC 140A High Speed Fuse
140FEE Eaton Bussmann 690VAC 140A High Speed Fuse

140FEE Eaton Bussmann 690VAC 140A High Speed Fuse

Share
pEaton Bussmann 140FEE, 690VAC, 140A high speed fuse, 200kA (a.c.) interrupting./p
    • Product Details
    • Download
    At a Glance
    • Rated current 140A
    • Rated voltage 690VAC
    • Interrupting rating 200kA (a.c.)

    The Eaton Bussmann 140FEE is a high speed fuse rated 690VAC at 140A and with a 200kA (a.c.) interrupting rating. It is used for DC links and semiconductor stacks that need sub-millisecond clearing. 140A, 690 VAC/500 VDC, High Speed Fuse, Class aR Fuse, Bussmann.

    Key Specifications

    Catalog Number140FEE
    SeriesBussmann BS88 FEE
    Product TypeBS88 high speed fuse link (bolted tags)
    Rated Voltage AC690V a.c. (IEC) / 700V a.c. (UL)
    Rated Voltage DC500V d.c.
    Rated Current140A
    Breaking Capacity200kA (a.c.)
    Pre-arcing I²t850 A²s
    Clearing I²t at 415 V / 660 V a.c.2500 / 3800 A²s
    Power Loss at Rated Current36 W
    StandardsBS88 part 4, IEC 60269-4, UL Recognized
    ApplicationProtection of power semiconductors, rectifiers, DC drives and power converters
    DimensionsFull size drawing ↓

    Applications

    Protection of power semiconductors, rectifiers, DC drives and power converters.

    DC links and semiconductor stacks that need sub-millisecond clearing.

    Selection Notes

    Match the fuse I²t to the device it protects; a larger fuse protects the cable but not the semiconductor.

    For DC circuits confirm the time constant, since clearing time depends on the circuit L/R.

    Common Questions

    What is the 140FEE rated for?

    It is rated 690VAC at 140A. The interrupting rating is 200kA (a.c.).

    What class is this fuse?

    The class is not stated on the manufacturer page; confirm on the datasheet before ordering.

    Can I replace it with a different class?

    No. Fuse classes differ in dimensions and rejection features, so a different class will not fit the holder and may not provide the same protection.

    What does the interrupting rating mean?

    It is the maximum fault current the fuse can safely interrupt. It must be at least as high as the available fault current at the installation point.

    How do I verify the part number?

    Order by the full catalog number 140FEE; suffixes change the terminal, voltage or package.

    Where can I find the datasheet?

    The manufacturer datasheet is the authority for derating curves, I²t and agency approvals for this catalog number.

    Source: manufacturer catalog page for 140FEE. Verify ratings against the current datasheet before ordering.