The Eaton Bussmann 160EET is a high speed fuse rated 690V (IEC) at 160A and with a 200kA RMS Sym, 50kA at 500Vdc interrupting rating. It is used for DC links and semiconductor stacks that need sub-millisecond clearing. Eaton Bussmann series high speed British standard fuse, Double barrel, 160A, 690 VAC/500 VDC (IEC), 700 VAC/500 VDC (UL), Class aR, Breaking capacity 200 kA RMS Sym.HS, 50 kA DC at 500 VDC.
| Product Name | Eaton Bussmann series high speed british standard fuse |
| Catalog Number | 160EET |
| Product Length/Depth | 94 mm |
| Product Height | 36 mm |
| Product Width | 20 mm |
| Product Weight | 91.6 g |
| Compliances | CE Marked RoHS Compliant |
| Certifications | IEC Rated UL Recognized Designed and tested to BS88 part 4 IEC 60269-4 |
| Rated Amperage | 160A |
| Rated Voltage | 690V (IEC), 700V (UL) |
| Rated voltage AC | 690V |
| Rated voltage DC | 500V |
| Interrupt Rating | 200kA RMS Sym, 50kA at 500Vdc |
| Class | Class aR |
| Pre-arc I²t | 1500 |
| Clearing I²t | 10000 at 415V, 17000 at 660V |
| Watt Losses | 39 W |
| Application | Semiconductor, DC Common bus, DC drives, power converters/rectifiers |
| Fuse Indicator | None |
| Suitable for | EC-600 Trip indicator kit (indicator + clips) TI700 Fuse indicator MAI Microswitch/adaptor MBI Microswitch/adaptor |
CE Marked RoHS Compliant, IEC Rated UL Recognized Designed and tested to BS88 part 4 IEC 60269-4 — as listed by the manufacturer for this catalog number. Confirm the current certificate before design freeze.
Semiconductor, DC Common bus, DC drives, power converters/rectifiers.
DC links and semiconductor stacks that need sub-millisecond clearing.
Match the fuse I²t to the device it protects; a larger fuse protects the cable but not the semiconductor.
For DC circuits confirm the time constant, since clearing time depends on the circuit L/R.
What is the 160EET rated for?
It is rated 690V (IEC) at 160A. The interrupting rating is 200kA RMS Sym, 50kA at 500Vdc. It is a Class aR fuse.
What class is this fuse?
Class aR.
Can I replace it with a different class?
No. Fuse classes differ in dimensions and rejection features, so a different class will not fit the holder and may not provide the same protection.
What does the interrupting rating mean?
It is the maximum fault current the fuse can safely interrupt. It must be at least as high as the available fault current at the installation point.
How do I verify the part number?
Order by the full catalog number 160EET; suffixes change the terminal, voltage or package.
Where can I find the datasheet?
The manufacturer datasheet is the authority for derating curves, I²t and agency approvals for this catalog number.
Source: manufacturer catalog page for 160EET. Verify ratings against the current datasheet before ordering.
Shenzhen Gaorunxin Technology Co., Ltd
Shenzhen Gaorunxin Technology Co., Ltd