250FM Eaton Bussmann 690VAC 250A High Speed Fuse
250FM Eaton Bussmann 690VAC 250A High Speed Fuse

250FM Eaton Bussmann 690VAC 250A High Speed Fuse

Share
Eaton Bussmann 250FM, 690VAC, 250A high speed fuse, 200kA (a.c.) interrupting.
    • Product Details
    • Download
    At a Glance
    • Rated current 250A
    • Rated voltage 690VAC
    • Interrupting rating 200kA (a.c.)

    The Eaton Bussmann 250FM is a high speed fuse rated 690VAC at 250A and with a 200kA (a.c.) interrupting rating. It is used for DC links and semiconductor stacks that need sub-millisecond clearing. 250A, 690 VAC/450VDC 200kA, high speed British standard fuse, Single barrel, Ceramic Fuse.

    Key Specifications

    Catalog Number250FM
    SeriesBussmann BS88 FM
    Product TypeBS88 high speed fuse link (bolted tags)
    Rated Voltage AC690V a.c. (IEC) / 700V a.c. (UL)
    Rated Voltage DC350–450V d.c.
    Rated Current250A
    Breaking Capacity200kA (a.c.)
    Pre-arcing I²t5200 A²s
    Clearing I²t at 415 V / 660 V a.c.20,500 / 37,500 A²s
    Power Loss at Rated Current48 W
    StandardsBS88 part 4, IEC 60269-4, UL Recognized
    ApplicationProtection of power semiconductors, rectifiers, DC drives and power converters
    DimensionsFull size drawing ↓

    Applications

    Protection of power semiconductors, rectifiers, DC drives and power converters.

    DC links and semiconductor stacks that need sub-millisecond clearing.

    Selection Notes

    Match the fuse I²t to the device it protects; a larger fuse protects the cable but not the semiconductor.

    For DC circuits confirm the time constant, since clearing time depends on the circuit L/R.

    Common Questions

    What is the 250FM rated for?

    It is rated 690VAC at 250A. The interrupting rating is 200kA (a.c.).

    What class is this fuse?

    The class is not stated on the manufacturer page; confirm on the datasheet before ordering.

    Can I replace it with a different class?

    No. Fuse classes differ in dimensions and rejection features, so a different class will not fit the holder and may not provide the same protection.

    What does the interrupting rating mean?

    It is the maximum fault current the fuse can safely interrupt. It must be at least as high as the available fault current at the installation point.

    How do I verify the part number?

    Order by the full catalog number 250FM; suffixes change the terminal, voltage or package.

    Where can I find the datasheet?

    The manufacturer datasheet is the authority for derating curves, I²t and agency approvals for this catalog number.

    Source: manufacturer catalog page for 250FM. Verify ratings against the current datasheet before ordering.

    Shenzhen Gaorunxin Technology Co., Ltd