| Part number | S500-315-R |
| Typical melting I2t | 0.58 A²s |
| End caps | silver-plated 32-125 mA, nickel-plated above |
| Element | single element |
| Voltage rating | 250 Vac |
| Breaking capacity | 35 A at 250 Vac, 290 A and 1,500 A on the higher ratings |
| Rated current | 315 mA |
| Body | Glass tube, 5 x 20 mm |
| Maximum voltage drop | 1,300 mV |
| AC interrupting rating | 35 A at 250 Vac |
| Design standard | IEC 60127-2 |
| Typical DC cold resistance | 3 Ω |
Read the row from the right: The typical cold resistance is 3 Ω, which is what the circuit sees before the element warms. Melting takes 0.58 A²s, so a fault has to deliver that much energy before the element even starts to go. At rated current the drop across it is 1,300 mV. The ratings on the left set the conditions under which those figures apply.
The failure mode of a fast fuse on the wrong load is a callout, not a fire. It opens on a start current that was always going to happen, the equipment goes dead at the worst moment, and the replacement does the same thing a week later.
The code breaks into three parts. S500 is the family, 315 is the ampere rating written in milliamps - which is 315 mA, not 315 amps - and -R is the RoHS suffix. Reading the middle group as amps is the single most common ordering error on this series.
Between a tenth of an amp and one amp the part is protecting a small power supply, a control transformer primary or a fan. This is the volume centre of the range and the rating most often held in stock, which makes it the natural starting point when a circuit has no previous fuse to match.
The step below is S500-250-R at 250 mA, the step above is S500-400-R at 400 mA. Between the three the body, the end caps and the breaking capacity are identical; only the element changes, so the choice is the load current and nothing else.
cURus (File E19180), VDE, BSI, IMQ, CCC, KC - the exact set depends on the rating.
Where the equipment ships into several markets, check each approval separately - the European and North American marks on this family do not always cover the same current range, and the gap is usually at the top of the range.
S500 and S501 look identical from the outside - both 5 x 20 mm - but S500 is glass with a low breaking capacity and S501 is ceramic with 1,500 A. On a mains input where the prospective fault is high, the glass part is the wrong choice even though it fits.
At 315 mA the part is a direct replacement for any other 5 x 20 mm fuse of the same rating and the same speed, regardless of maker. The body size is standardised; the only things that must match are the ampere rating, the speed and the voltage.
Can I use a fast-acting fuse where a time-delay one was fitted?
Physically yes, and that is exactly the problem. It will nuisance-trip on the first motor start, and the usual fix - fitting a larger rating - leaves the circuit protected at the wrong current.
What does the -R suffix mean?
It is the RoHS designation. The part is lead-free and compliant with the directive. Electrically it is identical to the non-R version, which is why both codes appear in older drawings.
What is the difference between the voltage ratings in the table?
The fuse has a different breaking capacity at each voltage. The higher the voltage across an opening fuse, the harder the arc is to extinguish, so the current it can safely interrupt falls as the voltage rises.
Design note: the ratings above are Technical Data 2052. Verify the exact rating, the voltage at which the breaking capacity applies, and the certificate for this current before release.

Dimensional drawing and recommended PCB pad layout from the Eaton data sheet. Tolerances and pad dimensions are as printed on the drawing; check the outline against your layout before release.