56ET Eaton Bussmann 450V 56A Semiconductor Fuse
56ET Eaton Bussmann 450V 56A Semiconductor Fuse

56ET Eaton Bussmann 450V 56A Semiconductor Fuse

Share
Eaton Bussmann 56ET, 450V, 56A semiconductor fuse, 200kA (a.c.) interrupting.
    • Product Details
    • Download
    At a Glance
    • Rated current 56A
    • Rated voltage 450V
    • Interrupting rating 200kA (a.c.)

    The Eaton Bussmann 56ET is a semiconductor fuse rated 450V at 56A and with a 200kA (a.c.) interrupting rating. It is used for rectifiers, drives and inverters where the fuse must protect the diode or thyristor. Eaton Bussmann high speed British standard fuse, 600 Vac, 450 Vdc, 56A, 200 kAIC, Blade end X blade end, Stud.

    Key Specifications

    Catalog Number56ET
    SeriesBussmann BS88 ET
    Product TypeBS88 high speed fuse link (bolted tags)
    Rated Voltage AC690V a.c. (IEC) / 700V a.c. (UL)
    Rated Voltage DC500V d.c.
    Rated Current56A
    Breaking Capacity200kA (a.c.)
    Pre-arcing I²t135 A²s
    Clearing I²t at 415 V / 660 V a.c.950 / 1500 A²s
    Power Loss at Rated Current14 W
    StandardsBS88 part 4, IEC 60269-4, UL Recognized
    ApplicationProtection of power semiconductors, rectifiers, DC drives and power converters
    DimensionsFull size drawing ↓

    Applications

    Protection of power semiconductors, rectifiers, DC drives and power converters.

    Rectifiers, drives and inverters where the fuse must protect the diode or thyristor.

    Selection Notes

    Size the fuse on the semiconductor's I²t, not on the load current — the fuse must clear before the die is damaged.

    Check the DC voltage derating: a fuse rated for AC duty often carries a lower DC rating.

    Common Questions

    What is the 56ET rated for?

    It is rated 450V at 56A. The interrupting rating is 200kA (a.c.).

    What class is this fuse?

    The class is not stated on the manufacturer page; confirm on the datasheet before ordering.

    Can I replace it with a different class?

    No. Fuse classes differ in dimensions and rejection features, so a different class will not fit the holder and may not provide the same protection.

    What does the interrupting rating mean?

    It is the maximum fault current the fuse can safely interrupt. It must be at least as high as the available fault current at the installation point.

    How do I verify the part number?

    Order by the full catalog number 56ET; suffixes change the terminal, voltage or package.

    Where can I find the datasheet?

    The manufacturer datasheet is the authority for derating curves, I²t and agency approvals for this catalog number.

    Source: manufacturer catalog page for 56ET. Verify ratings against the current datasheet before ordering.