5CLE-10E-D Eaton Bussmann 5.5kV 10A Class E Medium Voltage Fuse
5CLE-10E-D Eaton Bussmann 5.5kV 10A Class E Medium Voltage Fuse

5CLE-10E-D Eaton Bussmann 5.5kV 10A Class E Medium Voltage Fuse

Share
pEaton Bussmann 5CLE-10E-D, 5.5kV 10A Class E medium voltage fuse, 63 kAIC interrupting. For transformer, feeder and switchgear protection./p
    • Product Details
    • Download

    5CLE-10E-D Eaton Bussmann 5.5kV 10A Class E Medium Voltage Fuse

    At a Glance
    • 5.5 kV rated voltage, 10 A rated current
    • 63 kAIC interrupting rating
    • Class E time-current characteristic

    The Eaton Bussmann 5CLE-10E-D is a fuse with 5.5 kV rated voltage, 10 A rated current, 63 kAIC interrupting capacity, carrying a Class E time-current characteristic.

    Specifications

    General specifications
    UPC786670006657
    Product Length/Depth22.5 in
    Product Height5 in
    Product Width6 in
    Product Weight10.4 lb
    Electrical rating
    Amperage Rating10 A
    Interrupt rating63 kAIC
    General information
    Special featuresIndoor/outdoor, single barrel

    Series Selection Table

    5CLE-10E-D series selection table
    Ampere ratings, dimensions and catalog numbers across the Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Energy and utility distribution
    • Industrial equipment
    • Photovoltaic systems

    Selection Notes

    • Check the voltage rating against the system voltage, and the interrupting rating against the available fault current, before specifying.

    Common Questions

    What are the ratings of the Eaton Bussmann 5CLE-10E-D?
    5.5 kV / 10 A, with a 63 kAIC interrupting rating.
    How much fault current can the 5CLE-10E-D interrupt?
    63 kAIC. The available fault current at the installation point must not exceed this value.
    What does Class E mean for the 5CLE-10E-D?
    Class E defines the fuse's time-current characteristic. E-rated fuses carry a defined melting curve so they coordinate predictably with upstream and downstream devices; mixing E and non-E ratings in one feeder defeats that coordination.
    How should I select the 5CLE-10E-D for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message