5CLE-80E Eaton Bussmann 5.5kV 80A Medium Voltage Fuse
5CLE-80E Eaton Bussmann 5.5kV 80A Medium Voltage Fuse

5CLE-80E Eaton Bussmann 5.5kV 80A Medium Voltage Fuse

Share
pEaton Bussmann 5CLE-80E, 5.5kV 80A medium voltage fuse, 50 kAIC interrupting. For transformer, feeder and switchgear protection./p
    • Product Details
    • Download

    5CLE-80E Eaton Bussmann 5.5kV 80A Medium Voltage Fuse

    At a Glance
    • 5.5 kV rated voltage, 80 A rated current
    • 50 kAIC interrupting rating

    The Eaton Bussmann 5CLE-80E is a medium voltage fuse with 5.5 kV rated voltage, 80 A rated current, 50 kAIC interrupting capacity.

    Specifications

    General specifications
    UPC782116072804
    Product Length/Depth22.5 in
    Product Height7.5 in
    Product Width6.25 in
    Product Weight9.6 lb
    Electrical rating
    Amperage Rating80 A
    Interrupt rating50 kAIC
    General information
    Special featuresIndoor/outdoor, single barrel

    Standards Reference

    • ANSI C37.46

    Series Selection Table

    5CLE-80E series selection table
    Ampere ratings, dimensions and catalog numbers across the Medium Voltage Fuse family, reproduced from the Eaton Bussmann datasheet.

    Applications

    • Energy and utility distribution
    • Photovoltaic systems
    • Transformer protection

    Selection Notes

    • Select against the available fault current at the installation point, not the load current — the interrupting rating has to exceed it with margin.
    • E-rated fuses follow a defined melting curve; pairing them with non-E-rated devices in the same feeder breaks coordination.

    Common Questions

    What are the ratings of the Eaton Bussmann 5CLE-80E?
    5.5 kV / 80 A, with a 50 kAIC interrupting rating.
    How much fault current can the 5CLE-80E interrupt?
    50 kAIC. The available fault current at the installation point must not exceed this value.
    Which standards does the 5CLE-80E comply with?
    It is referenced against ANSI C37.46 in the manufacturer data.
    How should I select the 5CLE-80E for a circuit?
    Match the voltage rating to the system voltage, keep the continuous current above the load current, and check that the interrupting rating exceeds the available fault current. In medium voltage work, select on the transformer or feeder fault level rather than the load current alone.

    Shenzhen Gaorunxin Technology Co., Ltd