| Parameter | Rating |
|---|---|
| Part number | AGC-1-1/2-R |
| Body | Glass tube, 1/4 x 1-1/4 in (6.3 x 32 mm) |
| AC interrupting rating | 100 A at 250 Vac; 10,000 A at 125 Vac; 1,000 A at 32 Vac |
| Design standard | UL 248-14 |
| Voltage rating | 250 Vac |
| Typical DC cold resistance | 0.077 Ω |
| Typical melting I2t | 9.023 A²s |
| End caps | nickel-plated brass |
| Element | single element |
| Rated current | 1.5 A (1-1/2 A) |
| Typical voltage drop | 0.218 V |
Engineers usually specify it for these duties:
What are the ratings of the AGC-1-1/2-R?
1.5 A continuous at 250 Vac, interrupting rating 100 A at 250 Vac; 10,000 A at 125 Vac; 1,000 A at 32 Vac.
Can the AGC-1-1/2-R be used on a higher fault-current circuit?
No — its interrupting rating is 100 A at 250 Vac; 10,000 A at 125 Vac; 1,000 A at 32 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.