Eaton 15KP280CA Transient Voltage Suppressor 280 V
Eaton 15KP280CA Transient Voltage Suppressor 280 V

Eaton 15KP280CA Transient Voltage Suppressor 280 V

Share
15KP280CA: transient voltage suppressor diode, 280 V standoff, 454.5 V clamp, 33.2 A pulse, 15000 W, bidirectional.
    • Product Details
    • Download

    Eaton 15KP280CA Transient Voltage Suppressor 280 V

    15KP280CA at a glance: transient voltage suppressor diode, 280 V standoff, 454.5 V clamp, 33.2 A pulse, 15000 W, bidirectional.

    Ratings at a Glance

    ParameterValue
    Orderable part number15KP280CA
    Standoff voltage (VR)280 V
    Leakage current at VR2 uA
    Breakdown voltage at IT311 V to 341 V
    Test current (IT)5 mA
    Clamping voltage at IPP454.5 V
    Peak pulse current33.2 A
    PolarityBidirectional
    Peak pulse power, 10/1000 us15000 W
    PackageP600 axial
    MountingThrough-hole
    Operating temperature-55 °C to +175 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data 11207

    Outline drawing, pad or lead geometry and the pulse derating curves are
    on the pages of Eaton Technical Data 11207; the package line above is the
    body the part is built in.

    What the Numbers Mean

    A TVS is chosen after the surge source is known. The pulse current in the table is the current the part can take, so the source impedance and the coupling network decide whether the clamp column is the number the protected circuit experiences.

    The breakdown window spans 9.646 percent, from 311 V to 341 V. Design against the minimum, because a part at the bottom of the window starts conducting first.

    At 280 V standing the leakage is at most 2 uA, so the part draws 0.56 mW on the rail. Small, but it is the number that matters on a battery input.

    Within the 15KPE family this is item 37 of 37 in the Eaton catalogue.

    Series Positioning

    Place it on the protected side of any series impedance, not behind it. A TVS behind a common mode choke protects the choke, which is usually the opposite of what the design intends.

    • The pulse current is quoted for one waveform. A different waveform changes the allowable current, and the derating curve, not the single number, is the guide.
    • The breakdown window is deliberately wide so that production spread does not leave parts conducting at the standoff voltage. Design to the minimum breakdown, not the typical.

    Frequently Asked Questions

    Does the peak pulse power rating apply to any surge?
    No. It is quoted for a 10/1000 microsecond waveform. A shorter pulse allows more current and a longer one less; the derating curve converts between them.

    How much capacitance does it add?
    Enough to matter on a fast line. A 1500 W part can be several thousand picofarads, which is fine on a supply rail and not fine on a USB or Ethernet pair.

    How do I pick the standoff voltage?
    Above the highest steady-state voltage the line can reach, including regulation, ripple and any temporary overvoltage the standard requires. Then check that the minimum breakdown voltage is still above that level, because production spread moves it down.