Eaton ABC-10-R 10 A Fast-Blow Cartridge Fuse, Ceramic, 1/4 x 1-1/4 in
Eaton ABC-10-R 10 A Fast-Blow Cartridge Fuse, Ceramic, 1/4 x 1-1/4 in

Eaton ABC-10-R 10 A Fast-Blow Cartridge Fuse, Ceramic, 1/4 x 1-1/4 in

Share
pEaton ABC-10-R — 10 A, 250 V, fast-acting ceramic cartridge fuse, 200 A at 250 Vac; 10,000 A at 125 Vac; 10,000 A at 125 Vdc interrupting./p
    • Product Details
    • Download

    Eaton ABC-10-R 10 A Fast-Blow Cartridge Fuse, Ceramic, 1/4 x 1-1/4 in

    Eaton ABC-10-R 10 A Fast-Blow Cartridge Fuse, Ceramic, 1/4 x 1-1/4 in belongs to the Eaton range. It carries 10 A, rated 250 Vac, uses a fast-acting element, in a ceramic body.

    Technical Data

    ParameterRating
    Part numberABC-10-R
    Typical voltage drop0.15 V
    AC interrupting rating200 A at 250 Vac; 10,000 A at 125 Vac; 10,000 A at 125 Vdc
    End capsnickel-plated brass
    Voltage rating250 Vac
    Typical DC cold resistance0.011 Ω
    Rated current10 A
    Typical melting I2t208.8 A²s
    Elementsingle element
    BodyCeramic tube, 1/4 x 1-1/4 in (6.4 x 31.7 mm)
    Voltage rating, DC125 Vdc
    Design standardUL 248-14

    Design Notes

    • Interrupting capability is 200 A at 250 Vac; 10,000 A at 125 Vac; 10,000 A at 125 Vdc — confirm the circuit's prospective fault current stays below this.
    • Fast element suits resistive and semiconductor loads rather than motors with high inrush.
    • Because it opens within milliseconds, downstream semiconductors see less let-through energy.
    • Ceramic body holds higher breaking capacity than glass at the same footprint.
    • It is the usual choice where prospective fault current is high.
    • Working voltage must stay at or below 250 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 10 A to stop nuisance trips — fix the cause instead.

    Where It Is Used

    Typical places this fuse turns up:

    • EV
    • surge

    Common Questions

    What are the ratings of the ABC-10-R?

    10 A continuous at 250 Vac, interrupting rating 200 A at 250 Vac; 10,000 A at 125 Vac; 10,000 A at 125 Vdc.

    Is the ABC-10-R fast-acting or time-delay?

    It is fast-acting. Expect it to open quickly on overload.

    Can the ABC-10-R be used on a higher fault-current circuit?

    No — its interrupting rating is 200 A at 250 Vac; 10,000 A at 125 Vac; 10,000 A at 125 Vdc. Choose a part whose breaking capacity exceeds the prospective fault current.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message

    Shenzhen Gaorunxin Technology Co., Ltd

    Related Products