| Parameter | Rating |
|---|---|
| Part number | AGC-3/4-R |
| Body | Glass tube, 1/4 x 1-1/4 in (6.3 x 32 mm) |
| Rated current | 750 mA (3/4 A) |
| End caps | nickel-plated brass |
| Element | single element |
| Voltage rating | 250 Vac |
| AC interrupting rating | 35 A at 250 Vac; 10,000 A at 125 Vac; 1,000 A at 32 Vac |
| Typical voltage drop | 0.309 V |
| Typical melting I2t | 1.716 A²s |
| Design standard | UL 248-14 |
| Typical DC cold resistance | 0.272 Ω |
Typical places this fuse turns up:
What are the ratings of the AGC-3/4-R?
750 mA continuous at 250 Vac, interrupting rating 35 A at 250 Vac; 10,000 A at 125 Vac; 1,000 A at 32 Vac.
Can the AGC-3/4-R be used on a higher fault-current circuit?
No — its interrupting rating is 35 A at 250 Vac; 10,000 A at 125 Vac; 1,000 A at 32 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.
Shenzhen Gaorunxin Technology Co., Ltd
Shenzhen Gaorunxin Technology Co., Ltd