| Parameter | Rating |
|---|---|
| Part number | AGC-7-R |
| Typical DC cold resistance | 0.012 Ω |
| AC interrupting rating | 200 A at 250 Vac; 10,000 A at 125 Vac; 1,000 A at 32 Vac |
| Typical melting I2t | 195.02 A²s |
| Voltage rating | 250 Vac |
| Rated current | 7 A |
| Element | single element |
| Design standard | UL 248-14 |
| Body | Glass tube, 1/4 x 1-1/4 in (6.3 x 32 mm) |
| Typical voltage drop | 0.159 V |
| End caps | nickel-plated brass |
Common installation contexts include:
What are the ratings of the AGC-7-R?
7 A continuous at 250 Vac, interrupting rating 200 A at 250 Vac; 10,000 A at 125 Vac; 1,000 A at 32 Vac.
Is the AGC-7-R fast-acting or time-delay?
It is fast-acting. Expect it to open quickly on overload.
Can the AGC-7-R be used on a higher fault-current circuit?
No — its interrupting rating is 200 A at 250 Vac; 10,000 A at 125 Vac; 1,000 A at 32 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.
Shenzhen Gaorunxin Technology Co., Ltd
Shenzhen Gaorunxin Technology Co., Ltd