| Parameter | Rating |
|---|---|
| Parameter | Value |
| Manufacturer / Series | Eaton / C308F Series |
| Orderable part number | C308F100mA |
| Ferrule part number | C308F100mA |
| Axial lead equivalent | C308F-V-100mA |
| Current rating | 100 mA |
| Voltage rating | 250 Vac / 250 Vdc |
| Interrupting rating | 4000 A @ 250 Vac/dc |
| Typical DC cold resistance | 2.87 Ohm |
| Typical melting I2t | 0.00087 A2s (measured at 10 In) |
| Colour coding | Yellow |
| Package | 3 x 8.4 mm ceramic tube, silver-plated brass end caps, optional axial leads |
| Operating temperature | -55 C to +125 C with derating |
| Agency / environmental | cURus recognition file E19180, guide JDYX2 / JDYX8; electrical performance to EN 60079-11 for intrinsically safe applications; RoHS compliant |
Engineers usually specify it for these duties:
Order code C308F100mA from Eaton, supplied in 3 x 8.4 mm ceramic tube, silver-plated brass end caps, optional axial leads. Confirm the exact suffix before release.
What are the ratings of the C308F100mA?
100 mA continuous at 250 Vac / 250 Vdc, interrupting rating 4000 A @ 250 Vac/dc.
Can the C308F100mA be used on a higher fault-current circuit?
No — its interrupting rating is 4000 A @ 250 Vac/dc. Choose a part whose breaking capacity exceeds the prospective fault current.
Shenzhen Gaorunxin Technology Co., Ltd
Shenzhen Gaorunxin Technology Co., Ltd