| Parameter | Rating |
|---|---|
| Parameter | Value |
| Orderable part number | C515-2-R |
| Rated current | 2 A |
| Voltage rating | 250 Vac |
| Typical DC cold resistance | 0.059 ohm |
| Interrupting rating | 100 A at 250 Vac; 10000 A at 125 Vac |
| Typical melting I2t | 60.256 A²s |
| Max voltage drop at rated current | 170 mV |
| Body | 5 x 15 mm axial |
| Terminals | Tinned copper leads |
| Speed | Time-Delay (UL 248-14) |
| RoHS | Compliant (-R suffix) |
Common installation contexts include:
What are the ratings of the C515-2-R?
2 A continuous at 250 Vac, interrupting rating 100 A at 250 Vac; 10000 A at 125 Vac.
Is the C515-2-R fast-acting or time-delay?
It is time-delay. It tolerates short inrush surges.
Can the C515-2-R be used on a higher fault-current circuit?
No — its interrupting rating is 100 A at 250 Vac; 10000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.