Eaton C515-500-R - 0.5 A Time-Delay Glass Fuse, 250 Vac
Eaton C515-500-R - 0.5 A Time-Delay Glass Fuse, 250 Vac

Eaton C515-500-R - 0.5 A Time-Delay Glass Fuse, 250 Vac

Share
pEaton C515-500-R — 0.5 A, 250 V, time-delay glass cartridge fuse, 35 A at 250 Vac; 10000 A at 125 Vac interrupting./p
    • Product Details
    • Download

    Eaton C515-500-R - 0.5 A Time-Delay Glass Fuse, 250 Vac

    Built by Eaton, the C515-500-R carries 0.5 A, rated 250 Vac, uses a time-delay element, in a glass body.

    Technical Data

    ParameterRating
    ParameterValue
    Orderable part numberC515-500-R
    Rated current0.5 A
    Voltage rating250 Vac
    Typical DC cold resistance0.54 ohm
    Interrupting rating35 A at 250 Vac; 10000 A at 125 Vac
    Typical melting I2t2.28 A²s
    Max voltage drop at rated current440 mV
    Body5 x 15 mm axial
    TerminalsTinned copper leads
    SpeedTime-Delay (UL 248-14)
    RoHSCompliant (-R suffix)

    Selection Notes

    • Interrupting capability is 35 A at 250 Vac; 10000 A at 125 Vac — confirm the circuit's prospective fault current stays below this.
    • Time-delay element rides through motor starting and capacitive inrush without nuisance opening.
    • Startup surges of several times rated current are tolerated for a short window.
    • Glass body lets you inspect the element after a fault.
    • Best kept for lower fault-current circuits where visual diagnosis matters.
    • Working voltage must stay at or below 250 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 0.5 A to stop nuisance trips — fix the cause instead.

    Typical Applications

    Engineers usually specify it for these duties:

    • surge
    • transformer

    Q&A

    What are the ratings of the C515-500-R?

    0.5 A continuous at 250 Vac, interrupting rating 35 A at 250 Vac; 10000 A at 125 Vac.

    Is the C515-500-R fast-acting or time-delay?

    It is time-delay. It tolerates short inrush surges.

    Can the C515-500-R be used on a higher fault-current circuit?

    No — its interrupting rating is 35 A at 250 Vac; 10000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.