Eaton C515-6-R 6 A Glass Tube Fuse, Time-Delay, 5 x 15 mm
Eaton C515-6-R 6 A Glass Tube Fuse, Time-Delay, 5 x 15 mm

Eaton C515-6-R 6 A Glass Tube Fuse, Time-Delay, 5 x 15 mm

Share
pEaton C515-6-R — 6 A, 125 V, time-delay glass cartridge fuse, 5 x 15 mm, 400 A at 125 Vac interrupting./p
    • Product Details
    • Download

    Eaton C515-6-R 6 A Glass Tube Fuse, Time-Delay, 5 x 15 mm

    Built by Eaton, the C515-6-R carries 6 A, rated 125 Vac, uses a time-delay element, in a glass body, measuring 5 x 15 mm.

    Technical Data

    ParameterRating
    ParameterValue
    Orderable part numberC515-6-R
    Rated current6 A
    Voltage rating125 Vac
    Typical DC cold resistance0.014 ohm
    Interrupting rating400 A at 125 Vac
    Typical melting I2t471.36 A²s
    Max voltage drop at rated current125 mV
    Body5 x 15 mm axial
    TerminalsTinned copper leads
    SpeedTime-Delay (UL 248-14)
    RoHSCompliant (-R suffix)

    Selection Notes

    • Interrupting capability is 400 A at 125 Vac — confirm the circuit's prospective fault current stays below this.
    • Time-delay element rides through motor starting and capacitive inrush without nuisance opening.
    • Startup surges of several times rated current are tolerated for a short window.
    • Glass body lets you inspect the element after a fault.
    • Best kept for lower fault-current circuits where visual diagnosis matters.
    • Footprint 5 x 15 mm — check clip or holder compatibility before substitution.
    • Working voltage must stay at or below 125 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 6 A to stop nuisance trips — fix the cause instead.

    Typical Applications

    Engineers usually specify it for these duties:

    • EV
    • transformer

    Q&A

    What are the ratings of the C515-6-R?

    6 A continuous at 125 Vac, interrupting rating 400 A at 125 Vac.

    Is the C515-6-R fast-acting or time-delay?

    It is time-delay. It tolerates short inrush surges.

    What size is the C515-6-R?

    It measures 5 x 15 mm. Match the holder or clip to this footprint.

    Can the C515-6-R be used on a higher fault-current circuit?

    No — its interrupting rating is 400 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.

    Shenzhen Gaorunxin Technology Co., Ltd