| Parameter | Rating |
|---|---|
| Part number | GMA-315-R |
| Rated current | 315 mA |
| Body | Glass tube, 5 x 20 mm |
| Voltage rating | 250 Vac |
| End caps | silver-plated brass 63-315 mA, nickel-plated 500 mA-15 A |
| AC interrupting rating | 35 A at 250 Vac; 10,000 A at 125 Vac |
| Element | single element |
| Typical melting I2t | 0.019 A²s |
| Design standard | UL/CSA 248-14 |
| Maximum voltage drop | 450 mV |
| Typical DC cold resistance | 0.839 Ω |
Typical places this fuse turns up:
What are the ratings of the GMA-315-R?
315 mA continuous at 250 Vac, interrupting rating 35 A at 250 Vac; 10,000 A at 125 Vac.
Is the GMA-315-R fast-acting or time-delay?
It is fast-acting. Expect it to open quickly on overload.
Can the GMA-315-R be used on a higher fault-current circuit?
No — its interrupting rating is 35 A at 250 Vac; 10,000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.