Eaton GMC-150-R 150 mA Medium Time-Lag 5 x 20 mm Glass Fuse
Eaton GMC-150-R 150 mA Medium Time-Lag 5 x 20 mm Glass Fuse

Eaton GMC-150-R 150 mA Medium Time-Lag 5 x 20 mm Glass Fuse

Share
pEaton GMC-150-R — 150 mA, 250 V, time-delay glass cartridge fuse, 5 x 20 mm, 35 A at 250 Vac; 10,000 A at 125 Vac interrupting./p
    • Product Details
    • Download

    Eaton GMC-150-R 150 mA Medium Time-Lag 5 x 20 mm Glass Fuse

    Built by Eaton, the GMC-150-R carries 150 mA, rated 250 Vac, uses a time-delay element, in a glass body, measuring 5 x 20 mm.

    Technical Data

    ParameterRating
    Part numberGMC-150-R
    Typical melting I2t0.022 A²s
    Typical DC cold resistance2.555 Ω
    BodyGlass tube, 5 x 20 mm
    Design standardUL/CSA 248-14
    Elementsingle element
    Voltage rating250 Vac
    Maximum voltage drop800 mV
    Rated current150 mA
    AC interrupting rating35 A at 250 Vac; 10,000 A at 125 Vac
    End capsnickel-plated brass

    Selection Notes

    • Interrupting capability is 35 A at 250 Vac; 10,000 A at 125 Vac — confirm the circuit's prospective fault current stays below this.
    • Time-delay element rides through motor starting and capacitive inrush without nuisance opening.
    • Startup surges of several times rated current are tolerated for a short window.
    • Glass body lets you inspect the element after a fault.
    • Best kept for lower fault-current circuits where visual diagnosis matters.
    • Footprint 5 x 20 mm — check clip or holder compatibility before substitution.
    • Working voltage must stay at or below 250 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 150 mA to stop nuisance trips — fix the cause instead.

    Typical Applications

    Engineers usually specify it for these duties:

    • EV
    • adapter
    • surge
    • transformer

    Q&A

    What are the ratings of the GMC-150-R?

    150 mA continuous at 250 Vac, interrupting rating 35 A at 250 Vac; 10,000 A at 125 Vac.

    Is the GMC-150-R fast-acting or time-delay?

    It is time-delay. It tolerates short inrush surges.

    What size is the GMC-150-R?

    It measures 5 x 20 mm. Match the holder or clip to this footprint.

    Can the GMC-150-R be used on a higher fault-current circuit?

    No — its interrupting rating is 35 A at 250 Vac; 10,000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.