    Eaton GMD-250-R 250 mA Fuse 250 Vac Time-Delay (5 x 20 mm) belongs to the Eaton range. It carries 250 mA, rated 250 Vac, uses a time-delay element, measuring 5 x 20 mm.

    Technical Data

    ParameterRating
    Part numberGMD-250-R
    Typical melting I2t0.4 A²s
    Typical DC cold resistance2.4 Ω
    Rated current250 mA (1/4 A)
    Design standardUL/CSA 248-14
    Voltage rating250 Vac
    AC interrupting rating35 A at 250 Vac; 10,000 A at 125 Vac
    Elementsingle element
    BodyGlass tube, 5 x 20 mm
    Maximum voltage drop950 mV
    End capsnickel-plated brass

    Design Notes

    • Interrupting capability is 35 A at 250 Vac; 10,000 A at 125 Vac — confirm the circuit's prospective fault current stays below this.
    • Time-delay element rides through motor starting and capacitive inrush without nuisance opening.
    • Startup surges of several times rated current are tolerated for a short window.
    • Footprint 5 x 20 mm — check clip or holder compatibility before substitution.
    • Working voltage must stay at or below 250 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 250 mA to stop nuisance trips — fix the cause instead.

    Where It Is Used

    Typical places this fuse turns up:

    • EV

    Common Questions

    What are the ratings of the GMD-250-R?

    250 mA continuous at 250 Vac, interrupting rating 35 A at 250 Vac; 10,000 A at 125 Vac.

    Is the GMD-250-R fast-acting or time-delay?

    It is time-delay. It tolerates short inrush surges.

    What size is the GMD-250-R?

    It measures 5 x 20 mm. Match the holder or clip to this footprint.

    Can the GMD-250-R be used on a higher fault-current circuit?

    No — its interrupting rating is 35 A at 250 Vac; 10,000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.