Eaton MDA-1/2-R 500 mA Slow-Blow Fuse - 1/4 x 1-1/4 in, 250 Vac
Eaton MDA-1/2-R 500 mA Slow-Blow Fuse - 1/4 x 1-1/4 in, 250 Vac

Eaton MDA-1/2-R 500 mA Slow-Blow Fuse - 1/4 x 1-1/4 in, 250 Vac

Share
pEaton MDA-1/2-R — 500 mA, 250 V, time-delay fuse, 200 A at 250 Vac; 10,000 A at 125 Vac interrupting./p
    • Product Details
    • Download

    Eaton MDA-1/2-R 500 mA Slow-Blow Fuse - 1/4 x 1-1/4 in, 250 Vac

    Eaton MDA-1/2-R 500 mA Slow-Blow Fuse - 1/4 x 1-1/4 in, 250 Vac belongs to the Eaton range. It carries 500 mA, rated 250 Vac, uses a slow-blow element.

    Technical Data

    ParameterRating
    Part numberMDA-1/2-R
    Voltage rating250 Vac
    Elementsingle element
    Typical DC cold resistance2,600 mΩ
    Typical melting I2t1.2 A²s
    End capsnickel-plated brass
    Rated current500 mA (1/2 A)
    BodyCeramic tube, 1/4 x 1-1/4 in (6.3 x 32 mm)
    Maximum voltage drop1,650 mV
    AC interrupting rating200 A at 250 Vac; 10,000 A at 125 Vac
    Design standardUL 248-14

    Design Notes

    • Interrupting capability is 200 A at 250 Vac; 10,000 A at 125 Vac — confirm the circuit's prospective fault current stays below this.
    • Working voltage must stay at or below 250 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 500 mA to stop nuisance trips — fix the cause instead.

    Where It Is Used

    Typical places this fuse turns up:

    • EV

    Common Questions

    What are the ratings of the MDA-1/2-R?

    500 mA continuous at 250 Vac, interrupting rating 200 A at 250 Vac; 10,000 A at 125 Vac.

    Is the MDA-1/2-R fast-acting or time-delay?

    It is slow-blow. It tolerates short inrush surges.

    Can the MDA-1/2-R be used on a higher fault-current circuit?

    No — its interrupting rating is 200 A at 250 Vac; 10,000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.