| Parameter | Rating |
|---|---|
| Part number | MDA-1/4-R |
| Typical melting I2t | 0.28 A²s |
| AC interrupting rating | 200 A at 250 Vac; 10,000 A at 125 Vac |
| Design standard | UL 248-14 |
| Rated current | 250 mA (1/4 A) |
| Voltage rating | 250 Vac |
| End caps | nickel-plated brass |
| Maximum voltage drop | 2,900 mV |
| Typical DC cold resistance | 9,100 mΩ |
| Body | Ceramic tube, 1/4 x 1-1/4 in (6.3 x 32 mm) |
| Element | single element |
Typical places this fuse turns up:
What are the ratings of the MDA-1/4-R?
250 mA continuous at 250 Vac, interrupting rating 200 A at 250 Vac; 10,000 A at 125 Vac.
Is the MDA-1/4-R fast-acting or time-delay?
It is time-delay. It tolerates short inrush surges.
Can the MDA-1/4-R be used on a higher fault-current circuit?
No — its interrupting rating is 200 A at 250 Vac; 10,000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.
Shenzhen Gaorunxin Technology Co., Ltd
Shenzhen Gaorunxin Technology Co., Ltd