| Parameter | Rating |
|---|---|
| Part number | MDA-20-R |
| Maximum voltage drop | 95 mV |
| Voltage rating, DC | 125 Vdc |
| Voltage rating | 250 Vac |
| Typical melting I2t | 483.5 A²s |
| AC interrupting rating | 200 A at 250 Vac; 10,000 A at 125 Vac |
| Body | Ceramic tube, 1/4 x 1-1/4 in (6.3 x 32 mm) |
| Typical DC cold resistance | 4.1 mΩ |
| Element | single element |
| End caps | nickel-plated brass |
| Design standard | UL 248-14 |
| Rated current | 20 A |
Common installation contexts include:
What are the ratings of the MDA-20-R?
20 A continuous at 125 Vdc, interrupting rating 200 A at 250 Vac; 10,000 A at 125 Vac.
Is the MDA-20-R fast-acting or time-delay?
It is slow-blow. It tolerates short inrush surges.
Can the MDA-20-R be used on a higher fault-current circuit?
No — its interrupting rating is 200 A at 250 Vac; 10,000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.