| Parameter | Rating |
|---|---|
| Part number | MDL-1/2-R |
| Element | single element |
| End caps | nickel-plated brass |
| Design standard | UL 248-14 |
| Rated current | 500 mA (1/2 A) |
| Typical melting I2t | 1.656 A²s |
| Typical DC cold resistance | 0.943 Ω |
| Voltage rating | 250 Vac |
| AC interrupting rating | 35 A at 250 Vac; 10,000 A at 125 Vac |
| Body | Glass tube, 1/4 x 1-1/4 in (6.4 x 31.7 mm) |
| Typical voltage drop | 1.27 V |
Typical places this fuse turns up:
What are the ratings of the MDL-1/2-R?
500 mA continuous at 250 Vac, interrupting rating 35 A at 250 Vac; 10,000 A at 125 Vac.
Is the MDL-1/2-R fast-acting or time-delay?
It is time-delay. It tolerates short inrush surges.
Can the MDL-1/2-R be used on a higher fault-current circuit?
No — its interrupting rating is 35 A at 250 Vac; 10,000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.