| Parameter | Rating |
|---|---|
| Part number | MDL-2-1/4-R |
| Element | single element |
| Typical DC cold resistance | 0.096 Ω |
| Body | Glass tube, 1/4 x 1-1/4 in (6.4 x 31.7 mm) |
| Voltage rating | 250 Vac |
| Typical voltage drop | 0.535 V |
| Rated current | 2.25 A (2-1/4 A) |
| Design standard | UL 248-14 |
| AC interrupting rating | 100 A at 250 Vac; 10,000 A at 125 Vac |
| End caps | nickel-plated brass |
| Typical melting I2t | 49.6 A²s |
Engineers usually specify it for these duties:
What are the ratings of the MDL-2-1/4-R?
2.25 A continuous at 250 Vac, interrupting rating 100 A at 250 Vac; 10,000 A at 125 Vac.
Is the MDL-2-1/4-R fast-acting or time-delay?
It is time-delay. It tolerates short inrush surges.
Can the MDL-2-1/4-R be used on a higher fault-current circuit?
No — its interrupting rating is 100 A at 250 Vac; 10,000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.
Shenzhen Gaorunxin Technology Co., Ltd
Shenzhen Gaorunxin Technology Co., Ltd