| Parameter | Rating |
|---|---|
| Part number | MDL-3-R |
| AC interrupting rating | 100 A at 250 Vac; 10,000 A at 125 Vac |
| Rated current | 3 A |
| Voltage rating | 250 Vac |
| Typical DC cold resistance | 0.057 Ω |
| Typical voltage drop | 0.345 V |
| End caps | nickel-plated brass |
| Design standard | UL 248-14 |
| Element | single element |
| Body | Glass tube, 1/4 x 1-1/4 in (6.4 x 31.7 mm) |
| Typical melting I2t | 67.5 A²s |
Typical places this fuse turns up:
What are the ratings of the MDL-3-R?
3 A continuous at 250 Vac, interrupting rating 100 A at 250 Vac; 10,000 A at 125 Vac.
Is the MDL-3-R fast-acting or time-delay?
It is slow-blow. It tolerates short inrush surges.
Can the MDL-3-R be used on a higher fault-current circuit?
No — its interrupting rating is 100 A at 250 Vac; 10,000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.
Shenzhen Gaorunxin Technology Co., Ltd
Shenzhen Gaorunxin Technology Co., Ltd