Eaton MDL-6-1/4-R 6.25 A 250 Vac Glass Time-Lag Fuse
Eaton MDL-6-1/4-R 6.25 A 250 Vac Glass Time-Lag Fuse

Eaton MDL-6-1/4-R 6.25 A 250 Vac Glass Time-Lag Fuse

Share
pEaton MDL-6-1/4-R — 6.25 A, 250 V, time-delay glass cartridge fuse, 200 A at 250 Vac; 10,000 A at 125 Vac interrupting./p
    • Product Details
    • Download

    Eaton MDL-6-1/4-R 6.25 A 250 Vac Glass Time-Lag Fuse

    Eaton MDL-6-1/4-R 6.25 A 250 Vac Glass Time-Lag Fuse belongs to the Eaton range. It carries 6.25 A, rated 250 Vac, uses a time-delay element, in a glass body.

    Technical Data

    ParameterRating
    Part numberMDL-6-1/4-R
    Rated current6.25 A (6-1/4 A)
    Elementsingle element
    Typical melting I2t38.7 A²s
    AC interrupting rating200 A at 250 Vac; 10,000 A at 125 Vac
    Typical voltage drop0.152 V
    Voltage rating250 Vac
    Design standardUL 248-14
    BodyGlass tube, 1/4 x 1-1/4 in (6.4 x 31.7 mm)
    Typical DC cold resistance0.02 Ω
    End capsnickel-plated brass

    Design Notes

    • Interrupting capability is 200 A at 250 Vac; 10,000 A at 125 Vac — confirm the circuit's prospective fault current stays below this.
    • Time-delay element rides through motor starting and capacitive inrush without nuisance opening.
    • Startup surges of several times rated current are tolerated for a short window.
    • Glass body lets you inspect the element after a fault.
    • Best kept for lower fault-current circuits where visual diagnosis matters.
    • Working voltage must stay at or below 250 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 6.25 A to stop nuisance trips — fix the cause instead.

    Where It Is Used

    Typical places this fuse turns up:

    • EV

    Common Questions

    What are the ratings of the MDL-6-1/4-R?

    6.25 A continuous at 250 Vac, interrupting rating 200 A at 250 Vac; 10,000 A at 125 Vac.

    Is the MDL-6-1/4-R fast-acting or time-delay?

    It is time-delay. It tolerates short inrush surges.

    Can the MDL-6-1/4-R be used on a higher fault-current circuit?

    No — its interrupting rating is 200 A at 250 Vac; 10,000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.