| Parameter | Rating |
|---|---|
| Part number | MDL-6-1/4-R |
| Rated current | 6.25 A (6-1/4 A) |
| Element | single element |
| Typical melting I2t | 38.7 A²s |
| AC interrupting rating | 200 A at 250 Vac; 10,000 A at 125 Vac |
| Typical voltage drop | 0.152 V |
| Voltage rating | 250 Vac |
| Design standard | UL 248-14 |
| Body | Glass tube, 1/4 x 1-1/4 in (6.4 x 31.7 mm) |
| Typical DC cold resistance | 0.02 Ω |
| End caps | nickel-plated brass |
Typical places this fuse turns up:
What are the ratings of the MDL-6-1/4-R?
6.25 A continuous at 250 Vac, interrupting rating 200 A at 250 Vac; 10,000 A at 125 Vac.
Is the MDL-6-1/4-R fast-acting or time-delay?
It is time-delay. It tolerates short inrush surges.
Can the MDL-6-1/4-R be used on a higher fault-current circuit?
No — its interrupting rating is 200 A at 250 Vac; 10,000 A at 125 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.