| Parameter | Value |
|---|---|
| Orderable part number | MOV10V550 |
| Varistor voltage at 1 mA | 910 V |
| Maximum continuous AC voltage | 550 Vrms |
| Maximum continuous DC voltage | 745 Vdc |
| Clamping voltage | 1500 V |
| Clamping current | 25 A |
| Maximum surge current, 8/20 us | 2500 A |
| Rated power | 0.4 W |
| Typical capacitance at 1 kHz | 110 pF |
| Maximum energy, 10/1000 us | 93 J |
| Maximum body diameter | 7.5 mm |
| Agency recognition | cURus (UL 1449) and TUV |
| Package | 10 mm disc |
| Mounting | Radial, through-hole |
| Operating temperature | -40 °C to +125 °C |
| Qualification | Commercial grade |
| RoHS | Compliant, halogen free |
| Data sheet | Eaton Technical Data ELX1287 |
Dimensions, recommended pad or hole pattern and the derating curves are
on the data sheet pages; the package line above gives the body size as Eaton states it.
This is a single-shot device in the sense that the joule rating is quoted for one pulse. A surge protector built around a disc survives because the pulses are rare, not because the part is unlimited; the derating curve states how many.
The clamp column works out at 1.65 times the varistor voltage: 1500 V at the rated current against 910 V at 1 mA. That ratio is what the downstream part has to survive, not the 910 V figure on the label.
The disc absorbs 93 J in a 10/1000 us pulse and carries 2500 A in an 8/20 us pulse. Those are single shot figures: the same part will take a fraction of the energy repeatedly.
At 0.4 W continuous rating the body can sit at the working voltage indefinitely. A 20 mm disc handles roughly 110 pF across the line, which matters on a signal-carrying pair but not on a mains input.
Within the MOV family this is item 32 of 71 in the Eaton catalogue.
Keep the leads short and do not sleeve them together: the loop area between the two leads is part of the clamping path, and folding them against each other is what keeps the inductance low.
Are these parts UL recognised?
Yes, the data sheet lists cURus to UL 1449 and TUV. The file numbers are on the agency page of the data sheet, and they cover the whole family.
How do I size the disc diameter?
From the energy, not the current. Estimate the joule content of the surge your source can deliver, add margin for repeated events, and pick the smallest disc that covers it; a larger disc also raises the capacitance across the line.
Why is the DC rating higher than the AC rating?
The AC rating is an RMS value, so the peak of the sine is 1.41 times higher. The DC rating is set at that peak plus margin, which is why a 130 Vac part is rated 170 Vdc.