MOVGT07V160K: integrated MOV / GDT device, 1020 V clamp, 5 pF, 21 J.
    • Product Details
    • Download

    Eaton MOVGT07V160K MOVGT Hybrid Protector 7 mm

    MOVGT07V160K at a glance: integrated MOV / GDT device, 1020 V clamp, 5 pF, 21 J.

    Specification Table

    ParameterValue
    Orderable part numberMOVGT07V160K
    UL volts150 Vac
    Recommended MCOV160 Vac
    UL MCOV200 Vac
    MOV voltage at 1 mA240(216~264) V
    GDT voltage at 100 V/s350(280~420) V
    Platform voltage at 1000 V/usmax. 430 V
    Peak voltage at 1000 V/usmax. 1020 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us1750 A
    Maximum energy, 10/1000 us21 J
    Capacitance at 1 kHz5 pF
    Package7 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    How to Read These Ratings

    This is a mains-input protector, not a board-level one. It is chosen for the first stage ahead of a differential filter, and its platform voltage is what the downstream 1 kV-rated parts have to survive.

    The MOV inside is a 240(216~264) V part and the GDT is a 350(280~420) V tube. In series the pair holds the surge at the platform voltage of 430 V, well under the peak 1020 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 14 of 160 in the Eaton catalogue.

    Positioning in the Range

    Mount it away from the signal ground reference. The GDT arc couples noise into anything nearby, and the platform voltage appears across the package during the event.

    • The platform voltage is a surge figure, not a continuous rating. Do not use it to size the working voltage of the circuit.
    • The platform voltage is the level the combination holds during the surge; size the downstream insulation against it, not against the GDT DC sparkover.

    Frequently Asked Questions

    Can it be used on DC?
    No. A GDT does not extinguish below its arc voltage, so on DC the follow current continues until the source is removed. This part is for AC mains input.

    What is the platform voltage?
    It is the voltage the pair holds while the surge current flows, measured at a 1000 V/microsecond edge. It sits between the MOV clamp and the GDT arc voltage, and it is the number the downstream insulation has to survive.

    What is the difference between UL volts and MCOV?
    UL volts is the maximum line voltage the part is listed for under UL 1449; MCOV is the maximum continuous operating voltage the MOV element can hold. The two are related but not identical, and both are listed.