Eaton MOVGT07V220K MOV / GDT Device 220 Vac
Eaton MOVGT07V220K MOV / GDT Device 220 Vac

Eaton MOVGT07V220K MOV / GDT Device 220 Vac

Share
MOVGT07V220K: integrated MOV / GDT device, 1020 V clamp, 5 pF, 28 J.
    • Product Details
    • Download

    Eaton MOVGT07V220K MOV / GDT Device 220 Vac

    MOVGT07V220K at a glance: integrated MOV / GDT device, 1020 V clamp, 5 pF, 28 J.

    Key Specifications

    ParameterValue
    Orderable part numberMOVGT07V220K
    UL volts210 Vac
    Recommended MCOV220 Vac
    UL MCOV280 Vac
    MOV voltage at 1 mA330(297~363) V
    GDT voltage at 100 V/s350(280~420) V
    Platform voltage at 1000 V/usmax. 580 V
    Peak voltage at 1000 V/usmax. 1020 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us1750 A
    Maximum energy, 10/1000 us28 J
    Capacitance at 1 kHz5 pF
    Package7 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    The Figures Explained

    The two devices are stacked in one package, so the coordination is fixed by the manufacturer rather than by the board designer. That removes the usual risk of picking a GDT whose sparkover sits too close to the MOV clamp.

    The MOV inside is a 330(297~363) V part and the GDT is a 350(280~420) V tube. In series the pair holds the surge at the platform voltage of 580 V, well under the peak 1020 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 20 of 160 in the Eaton catalogue.

    Series Positioning

    Mount it away from the signal ground reference. The GDT arc couples noise into anything nearby, and the platform voltage appears across the package during the event.

    • The GDT will not extinguish at DC. On a DC input the follow current keeps the tube conducting until the source is interrupted, so this part belongs on AC mains only.
    • The platform voltage is the level the combination holds during the surge; size the downstream insulation against it, not against the GDT DC sparkover.

    Frequently Asked Questions

    What is the platform voltage?
    It is the voltage the pair holds while the surge current flows, measured at a 1000 V/microsecond edge. It sits between the MOV clamp and the GDT arc voltage, and it is the number the downstream insulation has to survive.

    What is the difference between UL volts and MCOV?
    UL volts is the maximum line voltage the part is listed for under UL 1449; MCOV is the maximum continuous operating voltage the MOV element can hold. The two are related but not identical, and both are listed.

    Does the GDT need a separate fuse?
    The follow current is limited by the source impedance and the upstream fuse. Check that the fuse clears the follow current, otherwise the tube keeps conducting after the surge.