Eaton MOVGT07V230K Coordinated MOV + GDT, 1320 V
Eaton MOVGT07V230K Coordinated MOV + GDT, 1320 V

Eaton MOVGT07V230K Coordinated MOV + GDT, 1320 V

Share
MOVGT07V230K: integrated MOV / GDT device, 1320 V clamp, 5 pF, 26 J.
    • Product Details
    • Download

    Eaton MOVGT07V230K Coordinated MOV + GDT, 1320 V

    MOVGT07V230K at a glance: integrated MOV / GDT device, 1320 V clamp, 5 pF, 26 J.

    Electrical Specifications

    ParameterValue
    Orderable part numberMOVGT07V230K
    UL volts190 Vac
    Recommended MCOV240 Vac
    UL MCOV250 Vac
    MOV voltage at 1 mA300(270~330) V
    GDT voltage at 100 V/s600(480~720) V
    Platform voltage at 1000 V/usmax. 530 V
    Peak voltage at 1000 V/usmax. 1320 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us1750 A
    Maximum energy, 10/1000 us26 J
    Capacitance at 1 kHz5 pF
    Package7 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    Reading the Data Sheet

    A gas discharge tube has a very low clamp but a slow, unpredictable trigger; a MOV has a fast trigger but a higher clamp. Putting them in series lets the MOV start the conduction and the GDT take the bulk of the current, which drops the residual voltage without losing the speed.

    The MOV inside is a 300(270~330) V part and the GDT is a 600(480~720) V tube. In series the pair holds the surge at the platform voltage of 530 V, well under the peak 1320 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 21 of 160 in the Eaton catalogue.

    Positioning in the Range

    The part is the first thing the surge sees, so it sits between the inlet and the fuse only if the fuse is rated for the follow current; otherwise the fuse goes first and the protector after it.

    • The series stack needs the MOV to hold off the line at the end of life as well. If the MOV degrades low in voltage the GDT starts to see the line, which is why the withstand count matters.
    • The MOV inside is a disc, so the energy rating follows the disc diameter; the GDT adds current capability, not joules.

    Frequently Asked Questions

    What is the platform voltage?
    It is the voltage the pair holds while the surge current flows, measured at a 1000 V/microsecond edge. It sits between the MOV clamp and the GDT arc voltage, and it is the number the downstream insulation has to survive.

    What is the difference between UL volts and MCOV?
    UL volts is the maximum line voltage the part is listed for under UL 1449; MCOV is the maximum continuous operating voltage the MOV element can hold. The two are related but not identical, and both are listed.

    Does the GDT need a separate fuse?
    The follow current is limited by the source impedance and the upstream fuse. Check that the fuse clears the follow current, otherwise the tube keeps conducting after the surge.

    Shenzhen Gaorunxin Technology Co., Ltd