Eaton MOVGT07V300K MOVGT Hybrid Protector 7 mm
Eaton MOVGT07V300K MOVGT Hybrid Protector 7 mm

Eaton MOVGT07V300K MOVGT Hybrid Protector 7 mm

Share
MOVGT07V300K: integrated MOV / GDT device, 1320 V clamp, 5 pF, 40 J.
    • Product Details
    • Download

    Eaton MOVGT07V300K MOVGT Hybrid Protector 7 mm

    MOVGT07V300K at a glance: integrated MOV / GDT device, 1320 V clamp, 5 pF, 40 J.

    Specification Table

    ParameterValue
    Orderable part numberMOVGT07V300K
    UL volts275 Vac
    Recommended MCOV300 Vac
    UL MCOV360 Vac
    MOV voltage at 1 mA430(387~473) V
    GDT voltage at 100 V/s600(480~720) V
    Platform voltage at 1000 V/usmax. 760 V
    Peak voltage at 1000 V/usmax. 1320 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us1750 A
    Maximum energy, 10/1000 us40 J
    Capacitance at 1 kHz5 pF
    Package7 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    The Figures Explained

    A gas discharge tube has a very low clamp but a slow, unpredictable trigger; a MOV has a fast trigger but a higher clamp. Putting them in series lets the MOV start the conduction and the GDT take the bulk of the current, which drops the residual voltage without losing the speed.

    The MOV inside is a 430(387~473) V part and the GDT is a 600(480~720) V tube. In series the pair holds the surge at the platform voltage of 760 V, well under the peak 1320 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 26 of 160 in the Eaton catalogue.

    What This Family Is For

    The part is the first thing the surge sees, so it sits between the inlet and the fuse only if the fuse is rated for the follow current; otherwise the fuse goes first and the protector after it.

    • The series stack needs the MOV to hold off the line at the end of life as well. If the MOV degrades low in voltage the GDT starts to see the line, which is why the withstand count matters.
    • The platform voltage is the level the combination holds during the surge; size the downstream insulation against it, not against the GDT DC sparkover.

    Frequently Asked Questions

    What is the difference between UL volts and MCOV?
    UL volts is the maximum line voltage the part is listed for under UL 1449; MCOV is the maximum continuous operating voltage the MOV element can hold. The two are related but not identical, and both are listed.

    Does the GDT need a separate fuse?
    The follow current is limited by the source impedance and the upstream fuse. Check that the fuse clears the follow current, otherwise the tube keeps conducting after the surge.

    Is the capacitance low enough for a signal line?
    A few picofarads, yes, but this is a mains protector. Its package and its platform voltage are chosen for an input stage, not for a data pair.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message

    Shenzhen Gaorunxin Technology Co., Ltd

    Related Products