Eaton MOVGT07V370K MOV / GDT Device 370 Vac
Eaton MOVGT07V370K MOV / GDT Device 370 Vac

Eaton MOVGT07V370K MOV / GDT Device 370 Vac

Share
MOVGT07V370K: integrated MOV / GDT device, 1320 V clamp, 5 pF, 49 J.
    • Product Details
    • Download

    Eaton MOVGT07V370K MOV / GDT Device 370 Vac

    MOVGT07V370K at a glance: integrated MOV / GDT device, 1320 V clamp, 5 pF, 49 J.

    Electrical Specifications

    ParameterValue
    Orderable part numberMOVGT07V370K
    UL volts350 Vac
    Recommended MCOV370 Vac
    UL MCOV460 Vac
    MOV voltage at 1 mA560(504~616) V
    GDT voltage at 100 V/s600(480~720) V
    Platform voltage at 1000 V/usmax. 986 V
    Peak voltage at 1000 V/usmax. 1320 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us1750 A
    Maximum energy, 10/1000 us49 J
    Capacitance at 1 kHz5 pF
    Package7 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    The Figures Explained

    The MOV part of the stack still does the continuous work: it holds the line voltage off the GDT and takes the first microseconds of the surge. The GDT takes over once the gap breaks down.

    The MOV inside is a 560(504~616) V part and the GDT is a 600(480~720) V tube. In series the pair holds the surge at the platform voltage of 986 V, well under the peak 1320 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 32 of 160 in the Eaton catalogue.

    Series Positioning

    Mount it away from the signal ground reference. The GDT arc couples noise into anything nearby, and the platform voltage appears across the package during the event.

    • A GDT has a statistical sparkover. The tolerance in the table is the spread over many units, not the repeatability of one unit.
    • The platform voltage is the level the combination holds during the surge; size the downstream insulation against it, not against the GDT DC sparkover.

    Frequently Asked Questions

    Does the GDT need a separate fuse?
    The follow current is limited by the source impedance and the upstream fuse. Check that the fuse clears the follow current, otherwise the tube keeps conducting after the surge.

    Is the capacitance low enough for a signal line?
    A few picofarads, yes, but this is a mains protector. Its package and its platform voltage are chosen for an input stage, not for a data pair.

    Why put a GDT in series with a MOV?
    The MOV triggers fast and the GDT clamps low. In series the MOV starts the conduction and the GDT carries the current, so the residual voltage is closer to the GDT arc voltage than to the MOV clamp.