| Parameter | Value |
|---|---|
| Orderable part number | MOVGT07V480K |
| UL volts | 460 Vac |
| Recommended MCOV | 480 Vac |
| UL MCOV | 600 Vac |
| MOV voltage at 1 mA | 750(675~825) V |
| GDT voltage at 100 V/s | 600(480~720) V |
| Platform voltage at 1000 V/us | max. 1320 V |
| Peak voltage at 1000 V/us | max. 1320 V |
| Withstand count at 2 kV / 1 kA | 40 shots |
| MOV withstand current, 8/20 us | 1750 A |
| Maximum energy, 10/1000 us | 64 J |
| Capacitance at 1 kHz | 5 pF |
| Package | 7 mm disc |
| Mounting | Radial, through-hole |
| Operating temperature | -40 °C to +105 °C |
| Qualification | Commercial grade |
| RoHS | Compliant, halogen free |
| Data sheet | Eaton Technical Data ELX1161 |
Dimensions, recommended pad or hole pattern and the derating curves are
on the data sheet pages; the package line above gives the body size as Eaton states it.
A gas discharge tube has a very low clamp but a slow, unpredictable trigger; a MOV has a fast trigger but a higher clamp. Putting them in series lets the MOV start the conduction and the GDT take the bulk of the current, which drops the residual voltage without losing the speed.
The MOV inside is a 750(675~825) V part and the GDT is a 600(480~720) V tube. In series the pair holds the surge at the platform voltage of 1320 V, well under the peak 1320 V it would reach alone at a 1000 V/us edge.
Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.
Within the MOVGT family this is item 38 of 160 in the Eaton catalogue.
The part is the first thing the surge sees, so it sits between the inlet and the fuse only if the fuse is rated for the follow current; otherwise the fuse goes first and the protector after it.
What is the platform voltage?
It is the voltage the pair holds while the surge current flows, measured at a 1000 V/microsecond edge. It sits between the MOV clamp and the GDT arc voltage, and it is the number the downstream insulation has to survive.
What is the difference between UL volts and MCOV?
UL volts is the maximum line voltage the part is listed for under UL 1449; MCOV is the maximum continuous operating voltage the MOV element can hold. The two are related but not identical, and both are listed.
Does the GDT need a separate fuse?
The follow current is limited by the source impedance and the upstream fuse. Check that the fuse clears the follow current, otherwise the tube keeps conducting after the surge.