Eaton MOVGT10V180K Coordinated MOV + GDT, 1320 V
Eaton MOVGT10V180K Coordinated MOV + GDT, 1320 V

Eaton MOVGT10V180K Coordinated MOV + GDT, 1320 V

Share
MOVGT10V180K: integrated MOV / GDT device, 1320 V clamp, 5 pF, 42 J.
    • Product Details
    • Download

    Eaton MOVGT10V180K Coordinated MOV + GDT, 1320 V

    MOVGT10V180K at a glance: integrated MOV / GDT device, 1320 V clamp, 5 pF, 42 J.

    Ratings at a Glance

    ParameterValue
    Orderable part numberMOVGT10V180K
    UL volts150 Vac
    Recommended MCOV180 Vac
    UL MCOV200 Vac
    MOV voltage at 1 mA240(216~264) V
    GDT voltage at 100 V/s600(480~720) V
    Platform voltage at 1000 V/usmax. 430 V
    Peak voltage at 1000 V/usmax. 1320 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us3500 A
    Maximum energy, 10/1000 us42 J
    Capacitance at 1 kHz5 pF
    Package10 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    What the Numbers Mean

    Because the GDT carries the follow current once it has fired, the combination survives repeated surges that would erode a MOV alone. The column to read is the withstand count at 2 kV / 1 kA rather than the single-shot peak current.

    The MOV inside is a 240(216~264) V part and the GDT is a 600(480~720) V tube. In series the pair holds the surge at the platform voltage of 430 V, well under the peak 1320 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 56 of 160 in the Eaton catalogue.

    What This Family Is For

    Mount it away from the signal ground reference. The GDT arc couples noise into anything nearby, and the platform voltage appears across the package during the event.

    • The series stack needs the MOV to hold off the line at the end of life as well. If the MOV degrades low in voltage the GDT starts to see the line, which is why the withstand count matters.
    • The platform voltage is the level the combination holds during the surge; size the downstream insulation against it, not against the GDT DC sparkover.

    Frequently Asked Questions

    What keeps the GDT from firing on the normal line voltage?
    The MOV holds off the continuous voltage, so the GDT only sees the line when the MOV is conducting. That coordination is what allows the series stack to sit across mains.

    How many surges will it take?
    The withstand column states the count at 2 kV / 1 kA, typically 40 shots. That is the number to design against, not the single-shot peak current of the MOV inside.

    Can it be used on DC?
    No. A GDT does not extinguish below its arc voltage, so on DC the follow current continues until the source is removed. This part is for AC mains input.