| Parameter | Value |
|---|---|
| Orderable part number | MOVGT10V230K |
| UL volts | 190 Vac |
| Recommended MCOV | 230 Vac |
| UL MCOV | 250 Vac |
| MOV voltage at 1 mA | 300(270~330) V |
| GDT voltage at 100 V/s | 600(480~720) V |
| Platform voltage at 1000 V/us | max. 530 V |
| Peak voltage at 1000 V/us | max. 1320 V |
| Withstand count at 2 kV / 1 kA | 40 shots |
| MOV withstand current, 8/20 us | 3500 A |
| Maximum energy, 10/1000 us | 54 J |
| Capacitance at 1 kHz | 5 pF |
| Package | 10 mm disc |
| Mounting | Radial, through-hole |
| Operating temperature | -40 °C to +105 °C |
| Qualification | Commercial grade |
| RoHS | Compliant, halogen free |
| Data sheet | Eaton Technical Data ELX1161 |
Dimensions, recommended pad or hole pattern and the derating curves are
on the data sheet pages; the package line above gives the body size as Eaton states it.
The MOV part of the stack still does the continuous work: it holds the line voltage off the GDT and takes the first microseconds of the surge. The GDT takes over once the gap breaks down.
The MOV inside is a 300(270~330) V part and the GDT is a 600(480~720) V tube. In series the pair holds the surge at the platform voltage of 530 V, well under the peak 1320 V it would reach alone at a 1000 V/us edge.
Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.
Within the MOVGT family this is item 61 of 160 in the Eaton catalogue.
The part is the first thing the surge sees, so it sits between the inlet and the fuse only if the fuse is rated for the follow current; otherwise the fuse goes first and the protector after it.
How many surges will it take?
The withstand column states the count at 2 kV / 1 kA, typically 40 shots. That is the number to design against, not the single-shot peak current of the MOV inside.
Can it be used on DC?
No. A GDT does not extinguish below its arc voltage, so on DC the follow current continues until the source is removed. This part is for AC mains input.
What is the platform voltage?
It is the voltage the pair holds while the surge current flows, measured at a 1000 V/microsecond edge. It sits between the MOV clamp and the GDT arc voltage, and it is the number the downstream insulation has to survive.