MOVGT10V300K: integrated MOV / GDT device, 1320 V clamp, 5 pF, 80 J.
    • Product Details
    • Download

    Eaton MOVGT10V300K MOVGT Hybrid Protector 10 mm

    MOVGT10V300K at a glance: integrated MOV / GDT device, 1320 V clamp, 5 pF, 80 J.

    Electrical Specifications

    ParameterValue
    Orderable part numberMOVGT10V300K
    UL volts275 Vac
    Recommended MCOV300 Vac
    UL MCOV360 Vac
    MOV voltage at 1 mA430(387~473) V
    GDT voltage at 100 V/s600(480~720) V
    Platform voltage at 1000 V/usmax. 760 V
    Peak voltage at 1000 V/usmax. 1320 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us3500 A
    Maximum energy, 10/1000 us80 J
    Capacitance at 1 kHz5 pF
    Package10 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    The Figures Explained

    The part is coordinated so the GDT does not see the continuous line voltage: the MOV holds off the normal operating level and the GDT only fires inside a surge. That is what makes the series connection possible at mains voltages.

    The MOV inside is a 430(387~473) V part and the GDT is a 600(480~720) V tube. In series the pair holds the surge at the platform voltage of 760 V, well under the peak 1320 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 66 of 160 in the Eaton catalogue.

    Series Positioning

    The part is the first thing the surge sees, so it sits between the inlet and the fuse only if the fuse is rated for the follow current; otherwise the fuse goes first and the protector after it.

    • A GDT has a statistical sparkover. The tolerance in the table is the spread over many units, not the repeatability of one unit.
    • The withstand count is stated at 2 kV / 1 kA because that is the combination the part is certified for. A different waveform changes the count.

    Frequently Asked Questions

    Does the GDT need a separate fuse?
    The follow current is limited by the source impedance and the upstream fuse. Check that the fuse clears the follow current, otherwise the tube keeps conducting after the surge.

    Is the capacitance low enough for a signal line?
    A few picofarads, yes, but this is a mains protector. Its package and its platform voltage are chosen for an input stage, not for a data pair.

    Why put a GDT in series with a MOV?
    The MOV triggers fast and the GDT clamps low. In series the MOV starts the conduction and the GDT carries the current, so the residual voltage is closer to the GDT arc voltage than to the MOV clamp.