MOVGT14V060K: integrated MOV / GDT device, 1020 V clamp, 5 pF, 27 J.
    • Product Details
    • Download

    Eaton MOVGT14V060K Integrated MOV GDT Protector

    MOVGT14V060K at a glance: integrated MOV / GDT device, 1020 V clamp, 5 pF, 27 J.

    Specification Table

    ParameterValue
    Orderable part numberMOVGT14V060K
    UL volts52 Vac
    Recommended MCOV60 Vac
    UL MCOV70 Vac
    MOV voltage at 1 mA82(74~90) V
    GDT voltage at 100 V/s350(280~420) V
    Platform voltage at 1000 V/usmax. 150 V
    Peak voltage at 1000 V/usmax. 1020 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us6000 A
    Maximum energy, 10/1000 us27 J
    Capacitance at 1 kHz5 pF
    Package14 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    What the Numbers Mean

    The MOV part of the stack still does the continuous work: it holds the line voltage off the GDT and takes the first microseconds of the surge. The GDT takes over once the gap breaks down.

    The MOV inside is a 82(74~90) V part and the GDT is a 350(280~420) V tube. In series the pair holds the surge at the platform voltage of 150 V, well under the peak 1020 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 82 of 160 in the Eaton catalogue.

    Where This Series Fits

    The part is the first thing the surge sees, so it sits between the inlet and the fuse only if the fuse is rated for the follow current; otherwise the fuse goes first and the protector after it.

    • A GDT has a statistical sparkover. The tolerance in the table is the spread over many units, not the repeatability of one unit.
    • The MOV inside is a disc, so the energy rating follows the disc diameter; the GDT adds current capability, not joules.

    Frequently Asked Questions

    Can it be used on DC?
    No. A GDT does not extinguish below its arc voltage, so on DC the follow current continues until the source is removed. This part is for AC mains input.

    What is the platform voltage?
    It is the voltage the pair holds while the surge current flows, measured at a 1000 V/microsecond edge. It sits between the MOV clamp and the GDT arc voltage, and it is the number the downstream insulation has to survive.

    What is the difference between UL volts and MCOV?
    UL volts is the maximum line voltage the part is listed for under UL 1449; MCOV is the maximum continuous operating voltage the MOV element can hold. The two are related but not identical, and both are listed.