Eaton MOVGT20V100K MOVGT Hybrid Protector 20 mm
Eaton MOVGT20V100K MOVGT Hybrid Protector 20 mm

Eaton MOVGT20V100K MOVGT Hybrid Protector 20 mm

Share
MOVGT20V100K: integrated MOV / GDT device, 708 V clamp, 5 pF, 106 J.
    • Product Details
    • Download

    Eaton MOVGT20V100K MOVGT Hybrid Protector 20 mm

    MOVGT20V100K at a glance: integrated MOV / GDT device, 708 V clamp, 5 pF, 106 J.

    Key Specifications

    ParameterValue
    Orderable part numberMOVGT20V100K
    UL volts95 Vac
    Recommended MCOV100 Vac
    UL MCOV120 Vac
    MOV voltage at 1 mA150(135~165) V
    GDT voltage at 100 V/s90(72~108) V
    Platform voltage at 1000 V/usmax. 270 V
    Peak voltage at 1000 V/usmax. 708 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us10000 A
    Maximum energy, 10/1000 us106 J
    Capacitance at 1 kHz5 pF
    Package20 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    How to Read These Ratings

    The MOV part of the stack still does the continuous work: it holds the line voltage off the GDT and takes the first microseconds of the surge. The GDT takes over once the gap breaks down.

    The MOV inside is a 150(135~165) V part and the GDT is a 90(72~108) V tube. In series the pair holds the surge at the platform voltage of 270 V, well under the peak 708 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 127 of 160 in the Eaton catalogue.

    Series Positioning

    The part is the first thing the surge sees, so it sits between the inlet and the fuse only if the fuse is rated for the follow current; otherwise the fuse goes first and the protector after it.

    • A GDT has a statistical sparkover. The tolerance in the table is the spread over many units, not the repeatability of one unit.
    • The MOV inside is a disc, so the energy rating follows the disc diameter; the GDT adds current capability, not joules.

    Frequently Asked Questions

    How many surges will it take?
    The withstand column states the count at 2 kV / 1 kA, typically 40 shots. That is the number to design against, not the single-shot peak current of the MOV inside.

    Can it be used on DC?
    No. A GDT does not extinguish below its arc voltage, so on DC the follow current continues until the source is removed. This part is for AC mains input.

    What is the platform voltage?
    It is the voltage the pair holds while the surge current flows, measured at a 1000 V/microsecond edge. It sits between the MOV clamp and the GDT arc voltage, and it is the number the downstream insulation has to survive.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message

    Shenzhen Gaorunxin Technology Co., Ltd

    Related Products