Eaton MOVGT20V120K MOV / GDT Device 120 Vac
Eaton MOVGT20V120K MOV / GDT Device 120 Vac

Eaton MOVGT20V120K MOV / GDT Device 120 Vac

Share
MOVGT20V120K: integrated MOV / GDT device, 710 V clamp, 5 pF, 130 J.
    • Product Details
    • Download

    Eaton MOVGT20V120K MOV / GDT Device 120 Vac

    MOVGT20V120K at a glance: integrated MOV / GDT device, 710 V clamp, 5 pF, 130 J.

    Key Specifications

    ParameterValue
    Orderable part numberMOVGT20V120K
    UL volts115 Vac
    Recommended MCOV120 Vac
    UL MCOV150 Vac
    MOV voltage at 1 mA180(162~198) V
    GDT voltage at 100 V/s90(72~108) V
    Platform voltage at 1000 V/usmax. 320 V
    Peak voltage at 1000 V/usmax. 710 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us10000 A
    Maximum energy, 10/1000 us130 J
    Capacitance at 1 kHz5 pF
    Package20 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    What the Numbers Mean

    The part is coordinated so the GDT does not see the continuous line voltage: the MOV holds off the normal operating level and the GDT only fires inside a surge. That is what makes the series connection possible at mains voltages.

    The MOV inside is a 180(162~198) V part and the GDT is a 90(72~108) V tube. In series the pair holds the surge at the platform voltage of 320 V, well under the peak 710 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 129 of 160 in the Eaton catalogue.

    What This Family Is For

    The series combination goes across the input at the first stage, ahead of the filter, with the GDT on the line side. Both devices carry the surge current, so the trace between them has to be as short and as wide as the incoming conductor.

    • The series stack needs the MOV to hold off the line at the end of life as well. If the MOV degrades low in voltage the GDT starts to see the line, which is why the withstand count matters.
    • The capacitance is a few picofarads, which is low enough for a mains input and low enough not to load a signal pair.

    Frequently Asked Questions

    How many surges will it take?
    The withstand column states the count at 2 kV / 1 kA, typically 40 shots. That is the number to design against, not the single-shot peak current of the MOV inside.

    Can it be used on DC?
    No. A GDT does not extinguish below its arc voltage, so on DC the follow current continues until the source is removed. This part is for AC mains input.

    What is the platform voltage?
    It is the voltage the pair holds while the surge current flows, measured at a 1000 V/microsecond edge. It sits between the MOV clamp and the GDT arc voltage, and it is the number the downstream insulation has to survive.