Eaton MOVGT20V360K Integrated MOV GDT Protector
Eaton MOVGT20V360K Integrated MOV GDT Protector

Eaton MOVGT20V360K Integrated MOV GDT Protector

Share
MOVGT20V360K: integrated MOV / GDT device, 1800 V clamp, 5 pF, 350 J.
    • Product Details
    • Download

    Eaton MOVGT20V360K Integrated MOV GDT Protector

    MOVGT20V360K at a glance: integrated MOV / GDT device, 1800 V clamp, 5 pF, 350 J.

    Ratings at a Glance

    ParameterValue
    Orderable part numberMOVGT20V360K
    UL volts300 Vac
    Recommended MCOV360 Vac
    UL MCOV390 Vac
    MOV voltage at 1 mA470(423~517) V
    GDT voltage at 100 V/s1000(800~1200) V
    Platform voltage at 1000 V/usmax. 830 V
    Peak voltage at 1000 V/usmax. 1800 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us10000 A
    Maximum energy, 10/1000 us350 J
    Capacitance at 1 kHz5 pF
    Package20 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    Reading the Data Sheet

    Because the GDT carries the follow current once it has fired, the combination survives repeated surges that would erode a MOV alone. The column to read is the withstand count at 2 kV / 1 kA rather than the single-shot peak current.

    The MOV inside is a 470(423~517) V part and the GDT is a 1000(800~1200) V tube. In series the pair holds the surge at the platform voltage of 830 V, well under the peak 1800 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 151 of 160 in the Eaton catalogue.

    Positioning in the Range

    The series combination goes across the input at the first stage, ahead of the filter, with the GDT on the line side. Both devices carry the surge current, so the trace between them has to be as short and as wide as the incoming conductor.

    • The series stack needs the MOV to hold off the line at the end of life as well. If the MOV degrades low in voltage the GDT starts to see the line, which is why the withstand count matters.
    • The capacitance is a few picofarads, which is low enough for a mains input and low enough not to load a signal pair.

    Frequently Asked Questions

    What is the difference between UL volts and MCOV?
    UL volts is the maximum line voltage the part is listed for under UL 1449; MCOV is the maximum continuous operating voltage the MOV element can hold. The two are related but not identical, and both are listed.

    Does the GDT need a separate fuse?
    The follow current is limited by the source impedance and the upstream fuse. Check that the fuse clears the follow current, otherwise the tube keeps conducting after the surge.

    Is the capacitance low enough for a signal line?
    A few picofarads, yes, but this is a mains protector. Its package and its platform voltage are chosen for an input stage, not for a data pair.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message