Eaton MOVGT20V520K Integrated MOV GDT Protector
Eaton MOVGT20V520K Integrated MOV GDT Protector

Eaton MOVGT20V520K Integrated MOV GDT Protector

Share
MOVGT20V520K: integrated MOV / GDT device, 1800 V clamp, 5 pF, 400 J.
    • Product Details
    • Download

    Eaton MOVGT20V520K Integrated MOV GDT Protector

    MOVGT20V520K at a glance: integrated MOV / GDT device, 1800 V clamp, 5 pF, 400 J.

    Key Specifications

    ParameterValue
    Orderable part numberMOVGT20V520K
    UL volts420 Vac
    Recommended MCOV520 Vac
    UL MCOV550 Vac
    MOV voltage at 1 mA680(612~748) V
    GDT voltage at 100 V/s1000(800~1200) V
    Platform voltage at 1000 V/usmax. 1200 V
    Peak voltage at 1000 V/usmax. 1800 V
    Withstand count at 2 kV / 1 kA40 shots
    MOV withstand current, 8/20 us10000 A
    Maximum energy, 10/1000 us400 J
    Capacitance at 1 kHz5 pF
    Package20 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1161

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    What the Numbers Mean

    This is a mains-input protector, not a board-level one. It is chosen for the first stage ahead of a differential filter, and its platform voltage is what the downstream 1 kV-rated parts have to survive.

    The MOV inside is a 680(612~748) V part and the GDT is a 1000(800~1200) V tube. In series the pair holds the surge at the platform voltage of 1200 V, well under the peak 1800 V it would reach alone at a 1000 V/us edge.

    Withstand is quoted as 40 shots at 2 kV / 1 kA. Because the GDT carries the follow current, the MOV is not eroded by the long tail of the pulse the way a stand-alone varistor is.

    Within the MOVGT family this is item 159 of 160 in the Eaton catalogue.

    Where This Series Fits

    Mount it away from the signal ground reference. The GDT arc couples noise into anything nearby, and the platform voltage appears across the package during the event.

    • A GDT has a statistical sparkover. The tolerance in the table is the spread over many units, not the repeatability of one unit.
    • The platform voltage is the level the combination holds during the surge; size the downstream insulation against it, not against the GDT DC sparkover.

    Frequently Asked Questions

    How many surges will it take?
    The withstand column states the count at 2 kV / 1 kA, typically 40 shots. That is the number to design against, not the single-shot peak current of the MOV inside.

    Can it be used on DC?
    No. A GDT does not extinguish below its arc voltage, so on DC the follow current continues until the source is removed. This part is for AC mains input.

    What is the platform voltage?
    It is the voltage the pair holds while the surge current flows, measured at a 1000 V/microsecond edge. It sits between the MOV clamp and the GDT arc voltage, and it is the number the downstream insulation has to survive.