| Parameter | Value |
|---|---|
| Orderable part number | MOVTP14V275T |
| Working voltage, DC | 350 Vdc |
| Working voltage, AC | 275 Vac |
| Varistor voltage at 1 mA | 387 V to 473 V |
| Clamping voltage, 8/20 us | 710 V at 50 A |
| Energy absorption, 10/1000 us | 170 J |
| Rated power | 0.6 W |
| Peak current, 8/20 us | 6000 A |
| Impulse response time | under 25 ns |
| Leakage current at 0.75 V1mA | max. 20 uA |
| Pin form | 3-lead, status contact on the third pin |
| Package | 14 mm disc |
| Mounting | Radial, through-hole |
| Operating temperature | -40 °C to +105 °C |
| Qualification | Commercial grade |
| RoHS | Compliant, halogen free |
| Data sheet | Eaton Technical Data ELX1079 |
Dimensions, recommended pad or hole pattern and the derating curves are
on the data sheet pages; the package line above gives the body size as Eaton states it.
The element is thermally coupled to the body, not to the current. That distinction matters: a slow overload that heats the disc without a large current still trips it, which a fuse in series would not see.
The clamp column works out at 1.65 times the varistor voltage: 710 V at the rated current against 430 V at 1 mA. That ratio is what the downstream part has to survive, not the 430 V figure on the label.
Standing at 350 V the leakage is at most 20 uA, which is 7 mW of continuous dissipation. Small, but it is why a varistor on a battery rail has to be chosen on leakage and not only on voltage.
The thermal element is the difference from a plain disc of the same rating. If the body overheats the element opens at 0.6 W of continuous overload, before the epoxy and the board around it are damaged.
The 3-lead form is the mechanical difference: the third pin brings the thermal contact out for monitoring. The electrical table is identical for both.
Within the MOVTP family this is item 8 of 28 in the Eaton catalogue.
Leave the clearance the drawing asks for. The thermal element is inside the package, but the heat that trips it has to come from the body, and a part pressed against a heatsink or a capacitor sees the wrong temperature.
What exactly opens inside the part?
A thermal element – a fuse or a spring contact – that is thermally coupled to the varistor body. When the body exceeds its limit the element opens and the part becomes an open circuit instead of a short.
Should I use the two-lead or the three-lead version?
Two-lead where the part only has to protect. Three-lead where the status has to be reported: the third pin carries the thermal contact out so a monitoring circuit can see that the protector has operated.
Does it reset after operation?
No. The element is one-shot, like a fuse. Once it opens the board has to be repaired, which is the intended behaviour: the alternative is a shorted MOV heating the board.
Shenzhen Gaorunxin Technology Co., Ltd
Shenzhen Gaorunxin Technology Co., Ltd