Eaton MOVTP14V320T Thermal Cut-off Varistor 410 Vdc
Eaton MOVTP14V320T Thermal Cut-off Varistor 410 Vdc

Eaton MOVTP14V320T Thermal Cut-off Varistor 410 Vdc

Share
MOVTP14V320T: thermally protected metal oxide varistor, 459-561 V varistor voltage, 410 V working, 845 V clamp, 209 J.
    • Product Details
    • Download

    Eaton MOVTP14V320T Thermal Cut-off Varistor 410 Vdc

    MOVTP14V320T at a glance: thermally protected metal oxide varistor, 459-561 V varistor voltage, 410 V working, 845 V clamp, 209 J.

    Electrical Specifications

    ParameterValue
    Orderable part numberMOVTP14V320T
    Working voltage, DC410 Vdc
    Working voltage, AC320 Vac
    Varistor voltage at 1 mA459 V to 561 V
    Clamping voltage, 8/20 us845 V at 50 A
    Energy absorption, 10/1000 us209 J
    Rated power0.6 W
    Peak current, 8/20 us6000 A
    Impulse response timeunder 25 ns
    Leakage current at 0.75 V1mAmax. 20 uA
    Pin form3-lead, status contact on the third pin
    Package14 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1079

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    What the Numbers Mean

    The element is thermally coupled to the body, not to the current. That distinction matters: a slow overload that heats the disc without a large current still trips it, which a fuse in series would not see.

    The clamp column works out at 1.66 times the varistor voltage: 845 V at the rated current against 510 V at 1 mA. That ratio is what the downstream part has to survive, not the 510 V figure on the label.

    Standing at 410 V the leakage is at most 20 uA, which is 8.2 mW of continuous dissipation. Small, but it is why a varistor on a battery rail has to be chosen on leakage and not only on voltage.

    The thermal element is the difference from a plain disc of the same rating. If the body overheats the element opens at 0.6 W of continuous overload, before the epoxy and the board around it are damaged.

    The 3-lead form is the mechanical difference: the third pin brings the thermal contact out for monitoring. The electrical table is identical for both.

    Within the MOVTP family this is item 12 of 28 in the Eaton catalogue.

    Positioning in the Range

    Leave the clearance the drawing asks for. The thermal element is inside the package, but the heat that trips it has to come from the body, and a part pressed against a heatsink or a capacitor sees the wrong temperature.

    • The third lead is not a second ground. Wiring it to the return defeats the monitoring function and can hold the thermal contact closed.
    • The part is a through-hole component with a defined lead form, so the hole pattern and the body height both come from the drawing.

    Frequently Asked Questions

    What exactly opens inside the part?
    A thermal element – a fuse or a spring contact – that is thermally coupled to the varistor body. When the body exceeds its limit the element opens and the part becomes an open circuit instead of a short.

    Should I use the two-lead or the three-lead version?
    Two-lead where the part only has to protect. Three-lead where the status has to be reported: the third pin carries the thermal contact out so a monitoring circuit can see that the protector has operated.

    Does it reset after operation?
    No. The element is one-shot, like a fuse. Once it opens the board has to be repaired, which is the intended behaviour: the alternative is a shorted MOV heating the board.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message

    Shenzhen Gaorunxin Technology Co., Ltd

    Related Products