MOVTP14V465T: thermally protected metal oxide varistor, 675-825 V varistor voltage, 615 V working, 1240 V clamp, 247 J.
    • Product Details
    • Download

    Eaton MOVTP14V465T MOVTP Varistor with Thermal Fuse

    MOVTP14V465T at a glance: thermally protected metal oxide varistor, 675-825 V varistor voltage, 615 V working, 1240 V clamp, 247 J.

    Ratings at a Glance

    ParameterValue
    Orderable part numberMOVTP14V465T
    Working voltage, DC615 Vdc
    Working voltage, AC465 Vac
    Varistor voltage at 1 mA675 V to 825 V
    Clamping voltage, 8/20 us1240 V at 50 A
    Energy absorption, 10/1000 us247 J
    Rated power0.6 W
    Peak current, 8/20 us6000 A
    Impulse response timeunder 25 ns
    Leakage current at 0.75 V1mAmax. 20 uA
    Pin form3-lead, status contact on the third pin
    Package14 mm disc
    MountingRadial, through-hole
    Operating temperature-40 °C to +105 °C
    QualificationCommercial grade
    RoHSCompliant, halogen free
    Data sheetEaton Technical Data ELX1079

    Dimensions, recommended pad or hole pattern and the derating curves are
    on the data sheet pages; the package line above gives the body size as Eaton states it.

    The Figures Explained

    Because the element is inside the package, the part behaves like an ordinary MOV until it operates. There is no holding current and no reset – after the event the circuit is open and the board has to be serviced.

    The clamp column works out at 1.65 times the varistor voltage: 1240 V at the rated current against 750 V at 1 mA. That ratio is what the downstream part has to survive, not the 750 V figure on the label.

    Standing at 615 V the leakage is at most 20 uA, which is 12.3 mW of continuous dissipation. Small, but it is why a varistor on a battery rail has to be chosen on leakage and not only on voltage.

    The thermal element is the difference from a plain disc of the same rating. If the body overheats the element opens at 0.6 W of continuous overload, before the epoxy and the board around it are damaged.

    The 3-lead form is the mechanical difference: the third pin brings the thermal contact out for monitoring. The electrical table is identical for both.

    Within the MOVTP family this is item 14 of 28 in the Eaton catalogue.

    Where This Series Fits

    In the three-lead version the third pin should be treated as a low-voltage signal: it is isolated from the line, but it runs close to it, so keep the creepage of the monitoring track in mind.

    • The thermal element protects against a shorted varistor, not against overvoltage. It does not replace the fuse, and it does not reset: once it opens the part is finished.
    • Agency recognition covers the varistor; the thermal element is part of the same approval and does not need a separate file.

    Frequently Asked Questions

    What approvals does it carry?
    The data sheet lists the agency file for the family. The thermal element is covered by the same approval as the varistor inside.

    What exactly opens inside the part?
    A thermal element – a fuse or a spring contact – that is thermally coupled to the varistor body. When the body exceeds its limit the element opens and the part becomes an open circuit instead of a short.

    Should I use the two-lead or the three-lead version?
    Two-lead where the part only has to protect. Three-lead where the status has to be reported: the third pin carries the thermal contact out so a monitoring circuit can see that the protector has operated.