| Parameter | Value |
|---|---|
| Orderable part number | MOVTP20V300T |
| Working voltage, DC | 385 Vdc |
| Working voltage, AC | 300 Vac |
| Varistor voltage at 1 mA | 423 V to 517 V |
| Clamping voltage, 8/20 us | 775 V at 100 A |
| Energy absorption, 10/1000 us | 350 J |
| Rated power | 1 W |
| Peak current, 8/20 us | 10000 A |
| Impulse response time | under 25 ns |
| Leakage current at 0.75 V1mA | max. 20 uA |
| Pin form | 3-lead, status contact on the third pin |
| Package | 20 mm disc |
| Mounting | Radial, through-hole |
| Operating temperature | -40 °C to +105 °C |
| Qualification | Commercial grade |
| RoHS | Compliant, halogen free |
| Data sheet | Eaton Technical Data ELX1079 |
Dimensions, recommended pad or hole pattern and the derating curves are
on the data sheet pages; the package line above gives the body size as Eaton states it.
The electrical ratings match an unprotected part of the same disc size, so the selection is unchanged. What changes is the space around the part: the thermal element needs clearance and the third lead needs a route.
The clamp column works out at 1.65 times the varistor voltage: 775 V at the rated current against 470 V at 1 mA. That ratio is what the downstream part has to survive, not the 470 V figure on the label.
Standing at 385 V the leakage is at most 20 uA, which is 7.7 mW of continuous dissipation. Small, but it is why a varistor on a battery rail has to be chosen on leakage and not only on voltage.
The thermal element is the difference from a plain disc of the same rating. If the body overheats the element opens at 1 W of continuous overload, before the epoxy and the board around it are damaged.
The 3-lead form is the mechanical difference: the third pin brings the thermal contact out for monitoring. The electrical table is identical for both.
Within the MOVTP family this is item 24 of 28 in the Eaton catalogue.
The protected part goes across the input downstream of the fuse, with the body clear of other heat sources. In the three-lead version the third pin is a signal, not a current path, and should be routed to the monitoring circuit rather than tied to ground.
What approvals does it carry?
The data sheet lists the agency file for the family. The thermal element is covered by the same approval as the varistor inside.
What exactly opens inside the part?
A thermal element – a fuse or a spring contact – that is thermally coupled to the varistor body. When the body exceeds its limit the element opens and the part becomes an open circuit instead of a short.
Should I use the two-lead or the three-lead version?
Two-lead where the part only has to protect. Three-lead where the status has to be reported: the third pin carries the thermal contact out so a monitoring circuit can see that the protector has operated.