    The S500-125-R from Eaton carries 125 mA, rated 250 Vac, uses a fast-acting element, in a glass body.

    Technical Data

    ParameterRating
    Part numberS500-125-R
    Typical DC cold resistance11 Ω
    Typical melting I2t0.0034 A²s
    End capssilver-plated 32-125 mA, nickel-plated above
    BodyGlass tube, 5 x 20 mm
    Breaking capacity35 A at 250 Vac, 290 A and 1,500 A on the higher ratings
    Elementsingle element
    Rated current125 mA (1/8 A)
    Maximum voltage drop2,200 mV
    Voltage rating250 Vac
    AC interrupting rating35 A at 250 Vac
    Design standardIEC 60127-2

    Practical Notes

    • Interrupting capability is 35 A at 250 Vac — confirm the circuit's prospective fault current stays below this.
    • Fast element suits resistive and semiconductor loads rather than motors with high inrush.
    • Because it opens within milliseconds, downstream semiconductors see less let-through energy.
    • Glass body lets you inspect the element after a fault.
    • Best kept for lower fault-current circuits where visual diagnosis matters.
    • Working voltage must stay at or below 250 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 125 mA to stop nuisance trips — fix the cause instead.

    Application Scenarios

    Common installation contexts include:

    • EV

    Questions and Answers

    What are the ratings of the S500-125-R?

    125 mA continuous at 250 Vac, interrupting rating 35 A at 250 Vac.

    Is the S500-125-R fast-acting or time-delay?

    It is fast-acting. Expect it to open quickly on overload.

    Can the S500-125-R be used on a higher fault-current circuit?

    No — its interrupting rating is 35 A at 250 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.