| Parameter | Rating |
|---|---|
| Part number | S500-630-R |
| Maximum voltage drop | 220 mV |
| Element | single element |
| Rated current | 630 mA |
| End caps | silver-plated 32-125 mA, nickel-plated above |
| Voltage rating | 250 Vac |
| Design standard | IEC 60127-2 |
| Typical melting I2t | 0.35 A²s |
| Breaking capacity | 35 A at 250 Vac, 290 A and 1,500 A on the higher ratings |
| Body | Glass tube, 5 x 20 mm |
| Typical DC cold resistance | 0.2 Ω |
| AC interrupting rating | 35 A at 250 Vac |
Typical places this fuse turns up:
What are the ratings of the S500-630-R?
630 mA continuous at 250 Vac, interrupting rating 35 A at 250 Vac.
Is the S500-630-R fast-acting or time-delay?
It is fast-acting. Expect it to open quickly on overload.
What size is the S500-630-R?
It measures 5 x 20 mm. Match the holder or clip to this footprint.
Can the S500-630-R be used on a higher fault-current circuit?
No — its interrupting rating is 35 A at 250 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.