Eaton S501-1-R 1 A Fast-Blow Cartridge Fuse, Ceramic, 5 x 20 mm
Eaton S501-1-R 1 A Fast-Blow Cartridge Fuse, Ceramic, 5 x 20 mm

Eaton S501-1-R 1 A Fast-Blow Cartridge Fuse, Ceramic, 5 x 20 mm

Share
pEaton S501-1-R — 1 A, 250 V, fast-acting ceramic cartridge fuse, 5 x 20 mm, 1,500 A at 250 Vac interrupting./p
    • Product Details
    • Download

    Eaton S501-1-R 1 A Fast-Blow Cartridge Fuse, Ceramic, 5 x 20 mm

    The S501-1-R from Eaton carries 1 A, rated 250 Vac, uses a fast-acting element, in a ceramic body, measuring 5 x 20 mm.

    Technical Data

    ParameterRating
    Part numberS501-1-R
    Typical DC cold resistance0.231 Ω
    End capssilver-plated 50-400 mA, nickel-plated 500 mA-10 A
    Rated current1 A
    Breaking capacity1,500 A at 250 Vac across the whole range
    AC interrupting rating1,500 A at 250 Vac
    Elementsingle element
    Typical melting I2t0.146 A²s
    Maximum voltage drop330 mV
    Voltage rating250 Vac
    Design standardIEC 60127-2
    BodyCeramic tube, 5 x 20 mm

    Practical Notes

    • Interrupting capability is 1,500 A at 250 Vac — confirm the circuit's prospective fault current stays below this.
    • Fast element suits resistive and semiconductor loads rather than motors with high inrush.
    • Because it opens within milliseconds, downstream semiconductors see less let-through energy.
    • Ceramic body holds higher breaking capacity than glass at the same footprint.
    • It is the usual choice where prospective fault current is high.
    • Footprint 5 x 20 mm — check clip or holder compatibility before substitution.
    • Working voltage must stay at or below 250 Vac; a lower-rated part is not a safe substitute.
    • Do not upsize beyond 1 A to stop nuisance trips — fix the cause instead.

    Application Scenarios

    Common installation contexts include:

    • EV

    Questions and Answers

    What are the ratings of the S501-1-R?

    1 A continuous at 250 Vac, interrupting rating 1,500 A at 250 Vac.

    Is the S501-1-R fast-acting or time-delay?

    It is fast-acting. Expect it to open quickly on overload.

    What size is the S501-1-R?

    It measures 5 x 20 mm. Match the holder or clip to this footprint.

    Can the S501-1-R be used on a higher fault-current circuit?

    No — its interrupting rating is 1,500 A at 250 Vac. Choose a part whose breaking capacity exceeds the prospective fault current.

    Shenzhen Gaorunxin Technology Co., Ltd

    Online message

    Shenzhen Gaorunxin Technology Co., Ltd

    Related Products