| Parameter | Rating |
|---|---|
| Parameter | Value |
| Orderable part number | S506-100-R (BK- prefix = 100 pcs carton, BK1- = 1,000 pcs polybag) |
| Typical voltage drop | 490 mV at rated current |
| Agency | cURus (E19180, JDYX2); SEMKO; VDE; BSI; IMQ; KC; CCC |
| Time-delay class | T (time-lag) |
| Dissipation at rating | 0.05 W |
| Body / package | 5 x 20 mm glass tube, nickel-plated brass end caps |
| Interrupting rating | 35 A at 250 Vac, 50 Hz |
| Voltage rating | 250 Vac |
| Current rating | 100 mA |
| Design standard | IEC 60127-1 and 60127-2 |
| Typical melting I2t | 0.045 A2s |
| Typical cold resistance | 2.8 Ohm |
Typical places this fuse turns up:
Order code S506-100-R from Eaton, supplied in 5 x 20 mm glass tube, nickel-plated brass end caps. Confirm the exact suffix before release.
What are the ratings of the S506-100-R?
100 mA continuous at 250 Vac, interrupting rating 35 A at 250 Vac, 50 Hz.
Is the S506-100-R fast-acting or time-delay?
It is time-delay. It tolerates short inrush surges.
Can the S506-100-R be used on a higher fault-current circuit?
No — its interrupting rating is 35 A at 250 Vac, 50 Hz. Choose a part whose breaking capacity exceeds the prospective fault current.